Section 14
Monitoring
14.7.3.2
14.7.3.3
444

Analog input signals

Up to 40 analog signals can be selected among internal analog and analog input signals.
PCM600 is used to configure the signals.
The analog trigger of Disturbance report is not affected if analog input M is to be included
in the disturbance recording or not (OperationM = Enabled/Disabled).
If OperationM = Disabled, no waveform (samples) will be recorded and reported in graph.
However, Trip value, pre-fault and fault value will be recorded and reported. The input
channel can still be used to trig the disturbance recorder.
If OperationM = Enabled, waveform (samples) will also be recorded and reported in
graph.
NomValueM: Nominal value for input M.
OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance report may
trig for high/low level of analog input M (Enabled) or not (Disabled).
OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relative
nominal value for analog input M in percent of nominal value.
Sub-function parameters
All functions are in operation as long as Disturbance report is in operation.
Indications
IndicationMaN: Indication mask for binary input N. If set (Show), a status change of that
particular input, will be fetched and shown in the disturbance summary on local HMI. If
not set (Hide), status change will not be indicated.
SetLEDN: Set yellow Pick up and red Trip LED on local HMI in front of the IED if binary
input N changes status.
Disturbance recorder
OperationM: Analog channel M is to be recorded by the disturbance recorder (Enabled)
or not (Disabled).
If OperationM = Disabled, no waveform (samples) will be recorded and reported in graph.
However, Trip value, pre-fault and fault value will be recorded and reported. The input
channel can still be used to trig the disturbance recorder.
If OperationM = Enabled, waveform (samples) will also be recorded and reported in
graph.
1MRK 506 334-UUS A
Application manual