Parameter
Keypad and
Parameter
structure
display
x.00
7.01
T5/6 analog input 1 level
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
FI
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Update rate
4ms write
7.02
T7 analog input 2 level
7.03
T8 analog input 3 level
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
FI
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Update rate
4ms write
When analog input 3 is in thermistor mode the display indicates the resistance of the thermistor as a percentage of 10KΩ
7.04
Stack temperature 1
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
FI
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Update rate
Background write
7.05
Stack temperature 2
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
FI
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Update rate
Background write
7.06
Control board temperature
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Bit
SP
FI
Coding
Open-loop, Closed-loop vector, Servo,
Range
Regen
Update rate
Background write
These parameters display the temperature of various parts of the drive in degrees Celsius. The power stage is monitored at two points (Pr 7.04 and
Pr 7.05) and the control board is also monitored (Pr 7.06). The following trips and alarms can are produced from the values in these parameters.
Parameter
Pr 7.04
Stack temperature 1 (IGBT)
Pr 7.05
Stack temperature 2 (power PCB)
Pr 7.06
Control board temperature
The threshold levels for the stack temperature trips and alarm vary between drive sizes.
The values displayed in the parameter are normally between -20 and +127°C. If the value measured from the thermistor exceeds the range from -20
to +150°C it is assumed that the device is either open-circuit or short-circuit.
Unidrive SP Advanced User Guide
Issue Number: 7
Parameter
Advanced parameter
description format
descriptions
DE
Txt VM DP
ND
RA
2
1
±100.00 %
DE
Txt VM DP
ND
RA
1
1
±100.0 %
DE
Txt VM
DP
ND
RA
1
-128 to 127
DE
Txt VM
DP
ND
RA
1
-128 to 127
DE
Txt VM DP
ND
RA
1
-128 to 127
Trip
"O.ht2" if Pr 7.04 > Trip threshold
(Can be reset if Pr 7.04 < Trip threshold – 5°C)
"O.ht2" if Pr 7.05 > Trip threshold
(Can be reset if Pr 7.05 < Trip threshold – 5°C)
"O.Ctl" if Pr 7.06 > 90°C
(Can be reset if Pr 7.04 < 85°C)
www.controltechniques.com
http://nicontrols.com
Serial comms
Electronic
Macros
protocol
nameplate
NC
NV
PT
US RW BU
1
1
NC
NV
PT
US RW BU
1
1
NC
NV
PT
US RW BU
1
1
o
C
NC
NV
PT
US RW BU
1
1
o
C
NC
NV
PT
US RW BU
1
1
1
o
C
"hot" if Pr 7.04 > Alarm threshold
"hot" if Pr 7.05 > Alarm threshold
"hot" if Pr 7.06 > 85°C
Feature look-
Performance
up table
PS
PS
PS
PS
PS
Alarm
Menu 7
137
Need help?
Do you have a question about the unidrive sp and is the answer not in the manual?