Parameter
Keypad and
Menu 5
structure
display
5.14
Voltage mode select
Drive modes
Open-loop
Bit
SP
FI
Coding
Range
Open-loop
Default
Open-loop
Update rate
Background read
0: Ur_S, Stator resistance and voltage offset measured at each start
The stator resistance (Pr 5.17) and the voltage offset (Pr 5.23) are measured and the parameters over-written each time the drive is started. This test
can only be done with a stationary machine where the flux has decayed to zero. Therefore this mode should only be used if the machine is
guaranteed to be stationary each time the drive is enabled. To prevent the test from being done before the flux has decayed there is a period of 1
second after the drive has been in the ready state during which the test is not done if the drive is re-started. In this case, previously measured values
are used. The new values of stator resistance and voltage offset are not automatically saved to EEPROM or the SMARTCARD.
1: Ur, No measurements
The stator resistance and voltage offset are not measured. The user can enter the motor and cabling resistance into the stator resistance parameter.
However this will not include resistance effects within the drive inverter. Therefore if this mode is to be used, it is best to use the auto-tuning stationary
test initially to measure the stator resistance.
2: Fd, Fixed boost mode.
Neither the stator resistance nor the voltage offset are used, instead a fixed characteristic with boost applied as defined by Pr 5.15 is used.
3: Ur_Auto, Stator resistance and voltage offset measured at first drive enable
The stator resistance and voltage offset are measured once, the first time the drive is enabled. After the test has been completed successfully the
mode is changed to Ur mode. The stator resistance and voltage offset are written to the parameters for the currently selected motor map and these
parameters along with this parameter are saved in the EEPROM (and the SMARTCARD if Pr 11.42 = 3 or 4). If the test fails the stator resistance and
voltage offset are not updated, the mode is changed to Ur, but no parameters are saved.
4: Ur_I, Stator resistance and voltage offset measured at each power-up
The stator resistance and voltage offset are measured when the drive is first enabled and at each subsequent power-up. The new values of stator
resistance and voltage offset are not automatically saved to EEPROM or the SMARTCARD.
5 E: Square law characteristic
Neither the stator resistance nor the voltage offset are used, instead a fixed square law characteristic with boost applied as defined by Pr 5.15 is used.
5.14
Action on enable
Drive modes
Servo
Bit
SP
FI
Coding
Range
Servo
Default
Servo
Update rate
Background read
This parameter defines the action taken on enable as follows:
0: nonE
No action.
1. Ph Enl
A minimal movement phasing test is performed each time the drive is enabled (i.e. changes from the inhibit state to either the stop or run state). The
test can be used to determine the phasing angle for an absolute or non-absolute type encoder. If the test is completed successfully the drive changes
to the stop or run state as appropriate. The phasing angle parameter is updated to the correct value, but it is not saved to EEPROM or the SMART
card.
2. Ph Init
A minimal movement phasing test is performed the first time the drive is enabled after power-up. The test will only be performed again on enable if the
position feedback device(s) have been re-initialised. Re-initialisation occurs for example after a trip specifically related to an encoder where position
information may have been lost. Initialisation occurs when parameter 03.48 changes from zero to one. The phasing angle parameter is updated to the
correct value, but it is not saved to EEPROM or the SMART card.
114
Parameter
Parameter
x.00
description format
DE
Txt VM DP
ND
RA
1
0 to 5
4
DE
TE
VM DP
ND
RA
1
0 to 2
0
www.controltechniques.com
http://nicontrols.com
Advanced parameter
Serial comms
Macros
descriptions
NC
NV
PT
US RW BU
1
1
NC
NV
PT
US RW BU
1
1
Electronic
Performance
protocol
nameplate
PS
1
PS
1