Terminal sizes and torque settings

To avoid a fire hazard and maintain validity of the UL listing, adhere to the specified tightening torques for the power and ground
terminals. Refer to the following tables.
WARNING
Table 3-21 Drive power terminal data
Powerdrive
AC and motor terminals
F300 frame
Recommended
size
Plug-in terminal block
3 and 4
0.7 N m (0.5 lb ft)
Plug-in terminal block
5
1.5 N m (1.1 lb ft)
M6 Nut (10 mm AF)
6
6.0 N m(4.4 Ib ft)
M8 Nut (13 mm AF)
7
12 N m (8.8 Ib ft)
M10 Nut (17 mm AF)
8 to 11
15 N m (11.1 Ib ft)
Table 3-22 Drive control and relay terminal data
Model
Connection type
All
Plug-in terminal block
Table 3-23 Plug-in terminal block maximum cable sizes
Model size
Terminal block description
11 way control connectors
All
2 way relay connector
3
6 way AC power connector
4
3 way AC power connector
5
3 way motor connector
6
7
2 way low voltage power
8
24 V supply connector
9A/9E
10E/11E
Powerdrive F300 User Guide
Issue Number: 2
Electrical
Getting
Basic
installation
started
parameters
the motor
Maximum
Recommended
0.8 N m (0.6 lb ft)
2.0 N m (1.4 Ib ft)
1.8 N m (1.3 lb ft)
1.5 N m (1.1 Ib ft)
8.0 N m (6.0 Ib ft)
6.0 N m(4.4 Ib ft)
14 N m (10.0 Ib ft)
12 N m (8.8 Ib ft)
20 N m (14.8 Ib ft)
15 N m (11.1 Ib ft)
Torque setting
0.5 N m (0.4 lb ft)
Max cable size
2
1.5 mm
(16 AWG)
2
2.5 mm
(12 AWG)
2
6 mm
(10 AWG)
2
8 mm
(8 AWG)
2
1.5 mm
(16 AWG)
Running
NV Media Card
Optimization
Operation
DC and braking
Maximum
T20 Torx (M4)
2.5 N m (1.8 Ib ft)
T20 Torx (M4) / M4 Nut (7 mm AF)
2.5 N m (1.8 Ib ft)
M6 Nut (10 mm AF)
8.0 N m (6.0 Ib ft)
M8 Nut (13 mm AF)
14 N m (10.0 Ib ft)
M10 Nut (17 mm AF)
20 N m (14.8 Ib ft)
Table 3-24 External EMC filter terminal data
CT part
number
Max cable
4200-1132
4200-0672
(1/0 AWG)
4200-1972
4200-1662
(3/0 AWG)
4200-0122
4200-0252
4200-0272
4200-0312
4200-0402
4200-3230
4200-3480
4200-2300
4200-4800
4200-3690
4200-3021
4200-4460
4200-1660
4200-2210
4200-0400
4200-0690
Onboard
Advanced
Technical
PLC
parameters
data
Ground terminal
Recommended
T20 Torx (M4) / M4 Nut (7 mm AF)
2.0 N m (1.4 Ib ft)
M5 Nut (8 mm AF)
2.0 N m (1.4 Ib ft)
M6 Nut (10 mm AF)
6.0 N m(4.4 Ib ft)
M8 Nut (13 mm AF)
12 N m (8.8 Ib ft)
M10 Nut (17 mm AF)
15 N m (11.1 Ib ft)
Power
connections
Ground
Max torque
size
stud size
2
8.0 N m
50 mm
(6.0lb ft)
M10
2
20 N m
95 mm
(14.8 lb ft)
2.3 N m
(1.7 lb ft)
2
16 mm
(6 AWG)
1.8 N m
(1.4 lb ft)
2
0.8 N m
4 mm
(0.59 lb ft)
(12 AWG)
2
0.8 N m
4 mm
(0.59 lb ft)
(12 AWG)
2
2.3 N m
16 mm
(1.70 Ib ft)
(6 AWG)
TBC
TBC
25 N m
TBC
(18.4 lb ft)
M10
TBC
TBC
25 N m
TBC
(18.4 lb ft)
TBC
TBC
M12
TBC
TBC
UL listing
Diagnostics
information
Maximum
2.5 N m (1.8 Ib ft)
5.0 N m (3.7 Ib ft)
8.0 N m (6.0 Ib ft)
14 N m (10.0 Ib ft)
20 N m (14.8 Ib ft)
Ground
connections
Max torque
18 N m
(13.3 lb ft)
5.0 N m
M6
(3.7 lb ft)
M5
2.5 N m
(1.8 lb ft)
M5
5.0 N m
M6
(3.7 lb ft)
TBC
TBC
TBC
TBC
25 N m
(18.4 lb ft)