Removal Of The Size 3/4/5/6 Internal Emc Filters; Removal Of Size 7,8,9A Internal Emc Filter And Line To Ground Varistor - Emerson Powerdrive F300 User Manual

Universal variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for Powerdrive F300:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
The supply must be disconnected before removing the
internal EMC filter.
WARNING
Figure 4-27 Removal of the size 3 internal EMC filter
Remove the screw and nut (1) and (2) as shown above.
Lift away from the securing points and rotate away from the drive.
Ensure the screw and nut are replaced and re-tightened with a
maximum torque of 2 N m (1.47 lb ft).
Figure 4-28 Removal of the size 4 internal EMC filter
To electrically disconnect the Internal EMC filter, remove the screw as
highlighted above (1).
Figure 4-29 Removal of the size 5 internal EMC filter
3
Remove the three M4 terminal nuts (1). Lift away the cover (2) to expose
the M4 Torx internal EMC filter removal screw. Finally remove the M4
Powerdrive F300 User Guide
Issue Number: 2
Electrical
Getting
Basic
installation
started
parameters
the motor
2
1
Running
NV Media Card
Optimization
Operation
Torx internal EMC filter removal screw (3) to electrically disconnect the
internal EMC filter.
Figure 4-30 Removal of the size 6 internal EMC filter
1
To electrically disconnect the Internal EMC filter, remove the screw as
highlighted above (1).
Figure 4-31 Removal of the size 7, 8 and 9A internal EMC filter and line to
ground varistors (size 7 shown)
To electrically disconnect the Internal EMC filter, remove the screw as
highlighted above (1).
To electrically disconnect the line to ground varistors, remove the screw
as highlighted above (2).
NOTE
The Internal EMC filter on size 9E, 10E and 11E cannot be removed.
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
2
UL listing
information
1
91

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents