Safety
Product
Mechanical
information
information
installation
Figure 4-37 Supply and ground cable clearance (size 7 onwards)
Ensure the AC supply and ground cables are at least 100 mm from the
power module and motor cable.
Figure 4-38 Sensitive signal circuit clearance
Avoid placing sensitive signal circuits in a zone 300 mm (12 in) in the
area immediately surrounding the power module. Ensure good EMC
grounding.
Powerdrive F300 User Guide
Issue Number: 2
Electrical
Getting
Basic
installation
started
parameters
the motor
100mm (4in)
100mm
(4in)
100mm (4in)
≥300 mm
(12 in)
Sensitive
signal
cable
Running
NV Media Card
Optimization
Operation
Figure 4-39 Grounding the drive, motor cable shield and filter
Motor cable shield
(unbroken) electrically
connected to and held
in place by grounding
clamp.
Connect the shield of the motor cable to the ground terminal of the motor
frame using a link that is as short as possible and not exceeding 50 mm
(2 in) long.