Onboard Plc Parameters - Emerson Powerdrive F300 User Manual

Universal variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for Powerdrive F300:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
10.4

Onboard PLC parameters

The following parameters are associated with the Onboard PLC user
program.
11.047
Onboard User Program: Enable
RW
Txt
Stop (0) or Run (1)
This parameter stops and starts the user program.
0 - Stop the User Program
The onboard user program is stopped. If it is restarted by setting
Onboard User Program: Enable (11.047) to a non-zero value the
background task starts from the beginning.
1 - Run the User Program
The user program will execute.
11.048
Onboard User Program: Status
RO
Txt
-2147483648 to
2147483647
This parameter is read-only and indicates the status of the user program
in the drive. The user program writes the value to this parameter.
0: Stopped
1: Running
2: Exception
3: No user program present
11.049
Onboard User Program: Programming Events
RO
Uni
0 to 65535
This parameter holds the number of times an Onboard PLC user
program download has taken place and is 0 on dispatch from the factory.
The drive is rated for one hundred ladder program downloads. This
parameter is not altered when defaults are loaded.
Onboard User Program: Freewheeling Tasks Per
11.050
Second
RO
Uni
0 to 65535
This parameter shows the number of times the freewheeling task has
started per second.
11.051
Onboard User Program: Clock Task Time Used
RO
0.0 to 100.0 %
This parameter shows the percentage of the available time used by the
user program clock task.
168
Electrical
Getting
Basic
installation
started
parameters
US
Run (1)
NC
PT
NC
PT
PS
NC
PT
NC
PT
Running
NV Media Card
Optimization
the motor
Operation
11.055
RO
0 to 262128 ms
This parameter shows the interval at which the clock task is scheduled to
run at in ms.
If the drive detects an error in the user program it will initiate a User
Program trip. The sub-trip number for the User Program trip details the
reason for the error. See Chapter 13 Diagnostics on page 260 for more
information on the User Program trip.
Onboard
Advanced
Technical
PLC
parameters
data
Onboard User Program: Clock Task Scheduled
Interval
NC
PT
Powerdrive F300 User Guide
UL listing
Diagnostics
information
Issue Number: 2

Hide quick links:

Advertisement

Table of Contents
loading