Table 2-2
400 V drive ratings (380 V to 480 V ±10 %)
Model
Frame size 3
Frame size 4
Frame size 5
Frame size 6
Frame size 7
Frame size 8
Frame size 9
Frame size 10
Frame size 11
* These ratings are for 2 kHz switching frequency. For ratings at 3 kHz switching frequency refer to section 12.1.1 Power and current ratings (Derating
for switching frequency and temperature) on page 232.
12
Electrical
Getting
Basic
installation
started
parameters
Maximum continuous
output current
A
03400034
3.4
03400045
4.5
03400062
6.2
03400077
7.7
03400104
10.4
03400123
12.3
04400185
18.5
04400240
24.0
05400300
30.0
06400380
38.0
06400480
48.0
06400630
63.0
07400790
79
07400940
94
07401120
112
08401550
155
08401840
184
09402210
221
09402660
266*
10403200
320
10403610
361
11404370
437
11404870
487*
11405070
507*
Running
NV Media Card
Optimization
the motor
Operation
Normal Duty
Nominal power
at 400 V
kW
1.1
1.5
2.2
3.0
4.0
5.5
7.5
11.0
15.0
18.5
22.0
30.0
37
45
55
75
90
110
132
160
200
225
250
280
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
Motor power
at 460 V
hp
1.5
2.0
3.0
5.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
40.0
50
60
75
100
125
150
200
250
300
350
400
450
Powerdrive F300 User Guide
UL listing
information
Peak current
A
3.7
4.9
6.8
8.4
11.4
13.5
20.3
26.4
33.0
41.8
52.8
69.3
86.9
103.4
123.2
170.5
202.4
243.1
292.6
352
397.1
480.7
535.7
557.7
Issue Number: 2