Emerson Powerdrive F300 User Manual page 100

Universal variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for Powerdrive F300:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
7
Analog output 1
8
Analog output 2
Terminal 7 default function
Terminal 8 default function
Type of output
AOI [AO2] Mode controlled by...
Operating in Voltage mode (default)
Voltage range
Maximum offset
Maximum output current
Load resistance
Protection
Operating in current mode
Current ranges
Common to all modes
Resolution
Sample / update period
9
0V common
Function
21
0V common
Function
100
Electrical
Getting
Basic
installation
started
parameters
OL> Motor FREQUENCY output
signal
RFC> SPEED output signal
Motor active current
Bipolar single-ended analog voltage or
unipolar current
Pr 07.024 [07.024]
±10 V ±5 %
±120 mV
±20 mA
≥1 k Ω
20 mA max. Short circuit protection
0 to 20 mA ±5%, 20 to 0 mA ±5%
4 to 20 mA ±5%, 20 to 4 mA ±5%
10-bit
250 µs (output will only change at update
the rate of the source parameter if slower)
Common connection for all external
devices
Common connection for all external
devices
Running
NV Media Card
Optimization
the motor
Operation
22
Digital I/O 1
23
Digital I/O 2
24
Digital I/O 3
Terminal 22 default function DRIVE ACTIVE output
Terminal 23 default function DRIVE RESET input
Terminal 24 default function RUN FORWARD input
Type
Input / output mode controlled by... Pr 08.031 , Pr 08.032 and Pr 08.033
Operating as an input
Logic mode controlled by...
Absolute maximum applied
voltage range
Impedance
Input thresholds
Operating as an output
Nominal maximum output current
Maximum output current
Common to all modes
Voltage range
Sample / Update period
25
Digital Input 4
26
Digital Input 5
Terminal 25 default function FIRE MODE ENABLE input
Terminal 26 default function Analog INPUT 1 / INPUT 2 select
Type
Logic mode controlled by...
Voltage range
Absolute maximum applied
voltage range
Impedance
Input thresholds
Sample / Update period
27
Digital Input 6
Terminal 27 default function Unassigned input
Type
Logic mode controlled by...
Voltage range
Absolute maximum applied
voltage range
Impedance
Input thresholds
Sample / Update period
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
Positive or negative logic digital inputs,
positive logic voltage source outputs
Pr 08.029
-3 V to +30 V
>2 mA @15 V from IEC 61131-2, type 1,
6.6 k Ω
10 V ±0.8 V from IEC 61131-2, type 1
100 mA (DIO1 & 2 combined)
100 mA (DIO3 & 24 V User Output
Combined)
100 mA
200 mA (total including all Digital I/O)
0 V to +24 V
2 ms (output will only change at the
update rate of the source parameter)
Negative or positive logic digital inputs
Pr 08.029
0 V to +24 V
-3 V to +30 V
>2 mA @15 V from IEC 61131-2, type 1,
6.6 k Ω
10 V ±0.8 V from IEC 61131-2, type 1
2 ms
Negative or positive logic digital inputs
Pr 08.029
0 V to +24 V
-3 V to +30 V
>2 mA @15 V from IEC 61131-2, type 1,
6.6 k Ω
10 V ±0.8 V from IEC 61131-2, type 1
2 ms
Powerdrive F300 User Guide
UL listing
information
Issue Number: 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents