Compliance With En 61800-3:2004; Compliance With Generic Emission Standards; Cable Layout; Drive Cable Clearances - Emerson Powerdrive F300 User Manual

Universal variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for Powerdrive F300:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation

Cable layout

Figure 4-35 indicates the clearances which should be observed around
the drive and related 'noisy' power cables by all sensitive control signals
/ equipment.
Figure 4-35 Drive cable clearances
Do not place sensitive
(unscreened) signal circuits
in a zone extending
300 mm (12") all around the
Drive, motor cable, input
cable from EMC filter and
unshielded braking resistor
cable (if used)
300 mm
(12 in)
N
NOTE
Any signal cables which are carried inside the motor cable (i.e. motor
thermistor) will pick up large pulse currents via the cable capacitance.
The shield of these signal cables must be connected to ground close to
the motor cable, to avoid this noise current spreading through the control
system.
4.10.5
Compliance with EN 61800-3:2004 (standard
for Power Drive Systems)
Meeting the requirements of this standard depends on the environment
that the drive is intended to operate in, as follows:
Operation in the first environment
Observe the guidelines given in section 4.10.6 Compliance with generic
emission standards on page 94. An external EMC filter will always be
required.
This is a product of the restricted distribution class according
to IEC 61800-3
In a residential environment this product may cause radio
interference in which case the user may be required to take
CAUTION
adequate measures.
Operation in the second environment
In all cases a shielded motor cable must be used, and an EMC filter is
required for all drives with a rated input current of less than 100 A.
94
Electrical
Getting
Basic
installation
started
parameters
Running
NV Media Card
Optimization
the motor
Operation
The drive contains an in-built filter for basic emission control. In some
cases feeding the motor cables (U, V and W) once through a ferrite ring
can maintain compliance for longer cable lengths.
For longer motor cables, an external filter is required. Where a filter is
required, follow the guidelines in Section 4.10.6 Compliance with generic
emission standards .
Where a filter is not required, follow the guidelines given in section
4.10.4 General requirements for EMC on page 93.
The second environment typically includes an industrial low-
voltage power supply network which does not supply
buildings used for residential purposes. Operating the drive in
this environment without an external EMC filter may cause
CAUTION
interference to nearby electronic equipment whose sensitivity
has not been appreciated. The user must take remedial
measures if this situation arises. If the consequences of
unexpected disturbances are severe, it is recommended that
the guidelines in Section 4.10.6 Compliance with generic
emission standards be adhered to.
Refer to section 12.1.26 Electromagnetic compatibility (EMC) on
page 255 for further information on compliance with EMC standards and
definitions of environments.
Detailed instructions and EMC information are given in the EMC Data
Sheet which is available from the supplier of the drive.
4.10.6

Compliance with generic emission standards

The following information applies to frame sizes 3 to 10.
Use the recommended filter and shielded motor cable. Observe the
layout rules given in Figure 4-36 and Figure 4-39. Ensure the AC supply
and ground cables are at least 100 mm from the power module and
motor cable.
Figure 4-36 Supply and ground cable clearance (sizes 3 to 6)
Do not modify
the filter wires
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
≥100 mm
(4 in)
≥100 mm
(4 in)
Powerdrive F300 User Guide
UL listing
information
Issue Number: 2