Parameter Reference Guide
 
Powerdrive F300
 
Open-Loop Mode
 
 
 
Issue: 01.15.00

Advertisement

loading

Summary of Contents for Emerson Powerdrive F300

  • Page 1       Parameter Reference Guide       Powerdrive F300       Open-Loop Mode               Issue: 01.15.00  ...
  • Page 2 Copyright © July 2016 Control Techniques Ltd Issue Number: 01.15.00 Powerdrive F300 Firmware Version: V01.15.00.00 Powerdrive F300 Project Last Modified: 20-Jul-2016 17:23:12 HTML Generator Version: 3.1.0.33376 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 3 If Parameter Cloning (11.042) has any other value it is not affected. The table below shows the possible actions that can be initiated with Parameter mm.000 (mm.000). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 4 This action does not require a drive reset. Only display parameters that are used to set-up destinations 12001 (i.e. DE format bit is 1). This action does not require a drive reset. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 5 Encoder electronic nameplate transfer from the encoder connected to drive P2 interface to the drive. Saving drive parameters User-save and power-down save drive parameters are stored in non-volatile memory within the drive. Any values that have changed are copied to this memory under the following conditions. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 6 A drive reset with 1233 in Parameter mm.000 (mm.000) loads the defaults defined for each parameter. If defaults are loaded with 1244 in Parameter mm.000 (mm.000) then the parameters in the table below have different defaults that are intended for the 60Hz regions. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 7 This ensures that the user program can be changed or erased in case it causes an HF trip at every power-up. Once the Stored HF is cleared, it is necessary to power cycle the drive or to re-download the user program to allow the program to restart. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 8 103.4 171.111 07401120 123.2 222.222 08401550 170.5 297.778 08401840 202.4 348.889 09402210 243.1 388.889 09402660 292.6 435.556 10403200 10403610 397.1 622.222 11404370 480.7 733.056 11404870 535.7 810.833 11405070 557.7 902.222 575V Rated Drives Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 9 50.6 84.444 07600520 57.2 97.778 07600730 80.3 08600860 94.6 08601080 118.8 191.111 09601250 137.5 202.222 09601550 170.5 254.722 10601720 189.2 291.667 10601970 216.7 346.111 11602250 247.5 408.333 11602750 302.5 462.778 11603050 335.5 511.389 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 10 Range applied to the parameters showing the AMC jerk Units User units / ms / ms / ms Range of [MIN] Range of [MAX] 107374.1823 VM_AMC_JERK_UNIPOLAR[MAX] = 107374.1823 / AMC Auto Resolution Scaling (31.016) VM_AMC_JERK_UNIPOLAR[MIN] = 0 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 11 Unipolar version of VM_AMC_POSITION Units User units Range of [MIN] Range of [MAX] 2147483647 VM_AMC_POSITION_UNIPOLAR is modified by AMC Auto Resolution Scaling (31.016) and AMC Roll Over Limit (31.010). See the table below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 12 VM_DC_VOLTAGE[MAX] is the full scale d.c. link voltage feedback (over voltage trip level) for the drive. This level is drive voltage rating dependent. See the table below. Voltage level 200V 400V 575V 690V VM_DC_VOLTAGE[MAX] 1190 VM_DC_VOLTAGE[MIN] = 0 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 13 User units Range of [MIN] Range of [MAX] 0 to 6 VM_MIN_SWITCHING_FREQUENCY[MAX] = Maximum Switching Frequency (05.018) VM_MIN_SWITCHING_FREQUENCY[MIN] = 0 for motor control modes, or 1 for Regen mode (subject to the maximum) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 14 Care should be taken not to exceed a speed that would cause damage to the position feedback device. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 15 -1000.0 to 0.0 Range of [MAX] 0.0 to 1000.0 VM_REGEN_REACTIVE[MAX] applies a limit to the reactive current reference in Regen mode so that the total current reference does not exceed its maximum allowed level. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 16 Unipolar version of VM_SPEED_FREQ_REF Open-loop: Hz Units RFC-A, RFC-S: rpm or mm/s Open-loop: 0.0 Range of [MIN] RFC-A, RFC-S: 0.0 Open-loop: 0.0 to 550.0 Range of [MAX] RFC-A, RFC-S: 0.0 to 50000.0 VM_SPEED_FREQ_REF_UNIPOLAR[MAX] = VM_SPEED_FREQ_REF[MAX] Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 17 Units User units Range of [MIN] Range of [MAX] 0 to 6 VM_SWITCHING_FREQUENCY[MAX] = Power stage dependent VM_SWITCHING_FREQUENCY[MIN] = 0 for motor control modes, or 1 for Regen mode (subject to the maximum) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 18 Range applied to torque reference and percentage load parameters with two decimal places Units Range of [MIN] -1000.00 to 0.00 Range of [MAX] 0.00 to 1000.00 VM_USER_CURRENT_HIGH_RES[MAX] = User Current Maximum Scaling (04.024) with an additional decimal place VM_USER_CURRENT_HIGH_RES[MIN] = -VM_USER_CURRENT_HIGH_RES[MAX] Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 19 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 20 Menu 1 − Frequency References Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 21 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 22 Update Rate 4ms write Display Format Standard Decimal Places Coding RO, VM, ND, NC, PT Reference Selected (01.001) is the basic reference selected from the available sources including the effect of the reference offset. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 23 (If Select Motor 2 Parameters (11.045) = 1 then M2 Minimum Reference Clamp (21.002) is used instead.) The minimum reference clamp is also used to provide the minimum speed limit for uni-polar mode (i.e. Bipolar Reference Enable (01.010) = 0) after the Reference Selected (01.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 24 01.014 Reference Selector Short description Defines the source for the references Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding RW, TE Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 25 If Reference Selected Indicator (01.049) = 4 the Keypad Control Mode Reference (01.017) is used and the sequencer operates in keypad mode where the start, stop and optionally the reverse selection functions are provided from the drive keypad. Jog Select (01.013) and Speed Feed-forwards Select (01.040) are always 0 when keypad mode is active. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 26 Defines the value for preset reference 2 Mode Open‑Loop Minimum −VM_SPEED_FREQ_REF Maximum VM_SPEED_FREQ_REF Default Units Type 32 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding RW, VM See Reference Selector (01.014). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 27 Defines the value for preset reference 8 Mode Open‑Loop Minimum −VM_SPEED_FREQ_REF Maximum VM_SPEED_FREQ_REF Default Units Type 32 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding RW, VM See Reference Selector (01.014). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 28 Defines the range either side of skip reference 3 to be implemented Mode Open‑Loop Minimum Maximum 25.0 Default Units Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, BU Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 29 Decimal Places Coding RO, VM, NC * A faster update rate of 250μs is possible for the speed reference from an analog input. See Menu 7 for details. Note that this parameter has higher Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 30 Defines which reference is selected by the drive Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate 4ms read Display Format Standard Decimal Places Coding RW, NC See Reference Selector (01.014). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 31 Displays which reference is currently selected Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit Volatile Update Rate 4ms write Display Format Standard Decimal Places Coding RO, ND, NC, PT See Reference Selector (01.014). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 32 (01.017). When Hand/Off/Auto mode is active the drive state and keypad keys are defined as shown in the tables below. Hand/Off/Auto state Equivalent normal state Ready with Reference Selected Indicator (01.049) = 4 Run with Reference Selected Indicator (01.049) = Hand Reference Selected Indicator (01.049) defined by Auto the reference selector system Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 33 Defines the reference value when fire mode is activated Mode Open‑Loop Minimum −VM_SPEED_FREQ_REF Maximum VM_SPEED_FREQ_REF Default Units Type 32 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, VM See Fire Mode Activate (01.054). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 34 If any of the trips shown as resettable occur, the drive will attempt to automatically reset the trip after 1s. Trip number Trip Resettable Over Volts OI ac OI Brake PSU 24V OHt Inverter EEPROM Fail User Save Power Down Save OI dc Slot1 HF Slot2 HF Slot3 HF 217-249 Slot4 HF Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 35 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 36 Menu 2 − Frequency Ramps Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 37 Ramp Mode (02.004) defines the ramp mode used for deceleration. During acceleration the frequency or speed changes are based on the final acceleration rate only. 0: Fast ramp During deceleration the frequency or speed changes are based on the final deceleration rate. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 38 If S Ramp Enable (02.006) = 0 linear ramps are used, but if S Ramp Enable (02.006) = 1 an acceleration limit is applied to give S ramps. See Maximum Rate Of Change Of Acceleration (02.007) for more details of S ramps. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 39 The following is an example based on the default parameter values for Open-loop mode. The diagram below shows a change of frequency from 0Hz to 50Hz with the ramp rate set to 5.0s/100Hz and Maximum Rate Of Change Of Acceleration (02.007) set to its default value of 3.1s /100Hz. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 40 If the required change of frequency had been 5.0Hz, i.e. less than 2 x wB, then the alternative equation should be used: = 2 √(Δw / J ) = 2 √(5.0 / 32.3) = 0.78s SRamp1 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 41 If 1 ≤ Acceleration Rate Selector (02.010) ≤ 8 the acceleration rate is selected directly, i.e. 1 selects Acceleration Rate 1 (02.011), 2 selects Acceleration Rate 2 (02.012), etc. If Acceleration Rate Selector (02.010) = 0 the acceleration rate is selected with the acceleration rate select bits as shown in the table below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 42 Defines the acceleration rate present in acceleration rate 4 Mode Open‑Loop Minimum −VM_ACCEL_RATE Maximum VM_ACCEL_RATE Default 20.0 Units Type 32 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding RW, VM Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 43 The Deceleration Rate Selector (02.020) operates in the same way as the Acceleration Rate Selector (02.010). If Deceleration Rate Selector (02.020) = 0 the deceleration rate is selected with the deceleration rate select bits as shown in the table below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 44 Defines the deceleration rate present in deceleration rate 4 Mode Open‑Loop Minimum −VM_ACCEL_RATE Maximum VM_ACCEL_RATE Default 20.0 Units Type 32 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding RW, VM See Deceleration Rate 1 (02.021). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 45 Coding RO, ND, NC, PT Deceleration Rate Selected (02.031) shows a value between 1 and 8 that corresponds to parameters 02.021 to 02.028 indicating which of these deceleration rates is actually being used. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 46 Defines which deceleration rate is used if deceleration rate selector = 0 Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate 4ms read Display Format Standard Decimal Places Coding RW, NC See Deceleration Rate Selector (02.020). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 47 If motor map 2 is selected then M2 Maximum Reference Clamp (21.001), M2 Acceleration Rate 1 (21.004) and M2 Deceleration Rate 1 (21.005) are used to define the ramp profile. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 48 See S Ramp Percentage (02.040). 2: Independent maximum rate of change of acceleration values The maximum rate of change of acceleration can be specified as four independent values. See Maximum Rate Of Change Of Acceleration 1 (02.042). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 49 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 50 If Absolute At Speed Select (03.009) = 1 absolute window mode is used. The "at speed" condition is true if, At Speed Lower Limit (03.006) ≤ |Post Ramp Reference (02.001)| ≤ At Speed Upper Limit (03.007) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 51 Indicates when the motor is running at speed Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding See At Speed Lower Limit (03.006). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 52 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 53 0.7 x Kc, provided Rated Current (05.007) is set to the MaxRef Maximum Heavy Duty Rating (11.032) or less. If Rated Current (05.007) is set to a higher level then the current limits can be adjusted so that the Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 54 In a drive that contains multiple power modules Full Scale Current Kc (11.061) is the full scale current of an individual module multiplied by the number of modules. Maximum Heavy Duty Rating (11.032) and Maximum Rated Current (11.060) are the value for an individual module multiplied by the number of modules. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 55 Decimal Places Coding RO, FI, VM, ND, NC, PT Current Magnitude (04.001) is the instantaneous drive output current scaled so that it represents the r.m.s. phase current in Amps under steady state conditions. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 56 The maximum possible current limit (VM_MOTOR1_CURRENT_LIMIT [MAX]) varies between drive sizes with default parameters loaded. For some drive sizes the default value may be reduced below the value given by the parameter range limiting. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 57 The system is forced into current control mode and the output of the d.c. bus voltage controller is fed into the current controller as shown below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 58 K is defined in more detail later. Motor Protection Accumulator So far the steady state motor losses have been defined, but the motor model must estimate the temperature within the motor under dynamically Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 59 If Rated Current (05.007) > Maximum Heavy Duty Rating (11.032) then K is defined as shown below. Two different characteristics are provided, but in both cases the motor performance is limited at lower speeds and the permissible overload is reduced from 105% to 101%. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 60 Motor Protection Accumulator Reset The initial value in the Motor Protection Accumulator (04.019) at power-up is defined by Motor Protection Accumulator Power-up Value (04.036) as given in the table below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 61 The current limit is derived from the current limit parameters (i.e. Motoring Current Limit (04.005), etc.) depending on the set-up and conditions. The current limit can be further limited by current limit on motor overload and/or drive temperature monitoring as shown below to give the Final Current Limit (04.018). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 62 Open‑Loop Minimum Maximum 100.0 Default Units Type 16 Bit Power Down Save Update Rate Background write Display Format Standard Decimal Places Coding RO, ND, NC, PT See Motor Thermal Time Constant 1 (04.015). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 63 (04.046) respectively). The drive will then include the core power loss in the torque calculation as PCoreLoss = No-load Core Loss (04.045) + (Rated Core Loss (04.046) - No-load Core Loss (04.045)) x (Torque Producing Current / Rated Torque Producing Current) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 64 Defines the low load detection speed/frequency threshold Mode Open‑Loop Minimum −VM_SPEED_FREQ_REF_UNIPOLAR Maximum VM_SPEED_FREQ_REF_UNIPOLAR Default Units Type 32 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, VM See Low Load Detection Level (04.027). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 65 Set to the rated iron losses of the motor as a percentage of the total losses for the motor Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding See Motor Thermal Time Constant 1 (04.015). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 66 The estimated torque (Percentage Torque (04.026)) is given as a percentage of Rated Torque (04.041). If Rated Torque (04.041) is left at the default value of zero then Percentage Torque (04.026) will remain at zero under all conditions. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 67 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 68 Menu 5 − Motor Control Mode: Open‑Loop The following table shows various definitions associated with controlling the motor. In each case the paramters used and the effect are given. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 69 16 Bit Volatile Update Rate Background read Display Format Standard Decimal Places Coding RO, FI, VM, ND, NC, PT D.c. Bus Voltage (05.005) gives the voltage across the d.c. link of the drive. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 70 2). If a linear position feedback device is used Number Of Motor Poles (05.011) should be set to 1 (2 Pole). If Number Of Motor Poles (05.011) = 0 the number of motor poles are calculated automatically as given below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 71 Defines the drive output mode, which can either be a voltage mode or a current mode Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, TE Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 72 6: Current 1P (Single phase current output) If this mode is selected it overrides all the normal control system for Open-loop mode and is used to produce a single phase square wave current output using the system shown below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 73 The steady state parameters are converted to equivalent transient model parameters: σL - (L The equivalent drive parameters are: Stator Resistance (05.017) = R Transient Inductance (05.024) = σL Stator Inductance (05.025) = L Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 74 Background read Display Format Standard Decimal Places Coding Voltage Controller Gain (05.031) can be used to modify the proportional gain of the d.c. link voltage controller used for standard ramp and supply loss control. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 75 Spin Start Boost (05.040) may need to be increased. If Spin Start Boost (05.040) is too small the drive will detect zero speed whatever the speed of the motor, and if Spin Start Boost (05.040) is too large the motor may accelerate away from standstill when the drive is enabled. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 76 If Reverse Output Phase Sequence (05.042) = 0 the output phase sequence is U-V-W when Output Frequency (05.001) is positive and W-V-U when Output Frequency (05.001) is negative. If Reverse Output Phase Sequence (05.042) = 1 the output phase sequence is reversed so that the phase sequence in W-V-U for positive frequencies and U-V-W for negative frequencies. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 77 Menu 6 Single Line Descriptions − Sequencer and Clock Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 78 400V drive: 330 V 06.066 Low Under Voltage Threshold ±VM_LOW_UNDER_VOLTS V RW Num 575V drive: 435 V 690V drive: 435 V 06.067 Low Under Voltage Threshold Select Off (0) or On (1) Off (0) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 79 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 80 Menu 6 − Sequencer and Clock Mode: Open‑Loop The diagram below shows the sequencer for Open-loop mode. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 81 The sequencer, which provides overall control of the drive, is implemented in two stages. The first stage includes the enable logic and sequencer logic Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 82 The diagram below shows the sequencer logic when Reference Selected Indicator (01.049) is not equal to 4 (i.e. keypad control mode is not selected). The definition of the logic symbols are given below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 83 The diagram below shows the sequencer logic when Reference Selected Indicator (01.049) = 4 (i.e. keypad control mode is selected). The definition of the logic symbols are given below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 84 Defines how the motor is controlled when the run signal is removed from the drive Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, TE Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 85 Defines the level of current used for injection braking Mode Open‑Loop Minimum Maximum 150.0 Default 100.0 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, RA Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 86 However, for this to work correctly it is assumed the motor is stationary when the drive is first power-up. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 87 1 Bit User Save Update Rate 2ms read Display Format Standard Decimal Places Coding RW, BU Drive Enable (06.015) must be active for the drive to be enabled. See description of enable logic. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 88 Defines which clock is used to display the current time, date and day of the week Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, TE Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 89 Filter Change Required / Change Done (06.022) is changed by the user from 1 to 0 the value of Time Between Filter Changes (06.021) is copied to Time Before Filter Change Due (06.023). For each hour while Drive Active (10.002) = 1 the Time Before Filter Change Due (06.023) is reduced by 1 until Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 90 Background read Display Format Standard Decimal Places Coding Running Cost (06.028) is derived from the Output Power (05.003) and the Energy Cost Per kWh (06.027) in cost per hour. The sign of Running Cost Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 91 Short description Set to 1 to give the drive a run signal Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate 2ms read Display Format Standard Decimal Places Coding RW, NC Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 92 If Control Word Enable (06.043) = 0 then Control Word (06.042) has no effect. If Control Word Enable (06.043) = 1 the bits in Control Word (06.042) are used instead of their corresponding parameters or to initiate drive functions as shown in the table below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 93 06.045 Cooling Fan control Short description Defines the maximum speed of the drive cooling fan Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 94 Short description Cooling Fan Speed Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit Volatile Update Rate Background Write Display Format Standard Decimal Places Coding RO, ND, NC, PT See Cooling Fan control (06.045). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 95 This can allow for the charge system in an external rectifier to complete the charging, or it can allow a Regen system to become synchronised. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 96 Defines the time that the drive will restartthe motor if the wake function is active Mode Open‑Loop Minimum Maximum 250.0 Default 10.0 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 97 X is between 1 and 3 and indicates the phase that is not connected or has a failed positive device (1 = U, 2 = V, 3 = W). If X is Powerdrive F300 Parameter Reference Guide...
  • Page 98 See exceptions below Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, VM, RA Voltage Default Value 200V 400V 575V 690V Under-voltage and power supply control Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 99 Standard Under Voltage Threshold (06.065) and the peak of the maximum allowed a.c. supply voltage for the drive. For example: The minimum Standard Under Voltage Threshold (06.065) for a 400V drive is 330V The maximum allowed supply voltage for this drive is 480V + 10% Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 100 (06.066) prevents this from being increased above Standard Under Voltage Threshold (06.065) / 1.1 so that the 5% hysteresis band on the low under- voltage threshold does not overlap the standard under-voltage threshold. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 101 2. Under-voltage System Contactor Close (06.069) is not set to one until the soft-start is fully active (relay open) because the soft-start is required to prevent current surges from the supply being applied. This is also shown in the diagram below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 102 The following diagram is a simple representation of the power circuit required. This does not include the necessary circuit protection components or possible battery charger, etc. The diagram below shows the state of Under Voltage Active (10.016) and the control signal to the external contactor (Under- voltage System Contactor Close (06.069)). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 103 This prevents power from being taken from the back-up supply if the mains supply is not present when the external soft-start system contactor is open. The following diagram shows how these differences apply to the system operation. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 104 06.070 Under-voltage System Contactor Closed Short description Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate 4ms read Display Format Standard Decimal Places Coding See Standard Under Voltage Threshold (06.065). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 105 Defines the lowest level of the d.c. bus voltage where the braking IGBT becomes active Mode Open‑Loop Minimum −VM_DC_VOLTAGE_SET Maximum VM_DC_VOLTAGE_SET Default See exceptions below Units Type 16 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding RW, VM, RA Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 106 Low Voltage Braking IGBT Threshold (06.075) is used, so that the braking IGBT is on with a minimum on time of 1ms is the d.c. link voltage is above this level, or off if the d.c. link voltage is below this level. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 107 UTC (Coordinated Universal Time) with an additional offset also provided by the option module. The data and time is derived by adding the additional offset and the time from the option module and then adding Date And Time Offset (06.084). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 108 Menu 7 Single Line Descriptions − Analog I/O Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 109 07.055 Analog Input 1 Thermistor Trip Threshold 0 to 5000 Ω 3300 Ω 07.056 Analog Input 1 Thermistor Reset Threshold 0 to 5000 Ω 1800 Ω 07.057 Analog Input 1 Thermistor Temperature -50 to 300 °C Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 110 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 111 Power Input 2 Regen Power Input 3 The diagram below shows the parameter structure for each I/O. See Internal I/O Identifier (11.068) for details of which I/O is present for different I/O options. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 112 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 113 Displays the temperature set up by Temperature Monitor Select 1 Mode Open‑Loop Minimum -250 Maximum Default Units °C Type 16 Bit Volatile Update Rate Background write Display Format Standard Decimal Places Coding RO, ND, NC, PT Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 114 Displays the temperature set up by Temperature Monitor Select 3 Mode Open‑Loop Minimum -250 Maximum Default Units °C Type 16 Bit Volatile Update Rate Background write Display Format Standard Decimal Places Coding RO, ND, NC, PT Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 115 = Analog Input 1 (07.001) + Analog Input 1 Offset (07.030) is the value after the offset has been applied and is limited between -100.00% and 100.00% Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 116 Display Format Standard Decimal Places Coding The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 117 Defines the scaling factor for analog output 1 Mode Open‑Loop Minimum 0.000 Maximum 10.000 Default 1.000 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding See Analog Output 1 Source (07.019). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 118 07.024 Analogue Output 2 Mode Short description Analogue Output 2 Mode Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Background Read Display Format Standard Decimal Places Coding RW, TE Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 119 If Analog Input 1 Mode (07.007) is set to any of the 4-20mA or 20-4mA modes and the current falls below 3mA then Analog Input 1 Current Loop Loss (07.028) is set to one. If the current is more than 3mA or any other mode is selected then Analog Input 1 Current Loop Loss (07.028) is set to zero. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 120 Inverter Temperature (07.034) shows the estimated junction temperature of the hottest power device within the drive inverter. If this temperature exceeds the switch down threshold defined for the power stage the switching frequency is reduced provided this feature has not been disabled (see Auto-switching Frequency Change (05.035)). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 121 00: D.c. link thermal model Control system 00: Braking IGBT thermal model Power system zz: Thermistor location defined by zz in the power system Power system Rectifier number zz: Thermistor location defined by zz in the rectifier Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 122 Defines the minimum value for analog input 2 Mode Open‑Loop Minimum 0.00 Maximum 100.00 Default 0.00 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding See Analog Input 1 (07.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 123 (07.007) is set up for temperature feedback mode. When a temperature feedback mode is selected 5V is applied to the output via a 3.3KOhm resistor to supply current through the temperature measurement device. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 124 (07.011) is set up for temperature feedback mode. When a temperature feedback mode is selected 5V is applied to the output via a 3.3KOhm resistor to supply current through the temperature measurement device. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 125 If Analog Input 2 Mode (07.011) is set up to select temperature measurement then Analog Input 2 Thermistor Temperature (07.062) shows the temperature of the device, otherwise Analog Input 2 Thermistor Temperature (07.062) = 0. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 126 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 127 The parameter structure for each digital I/O is shown in the diagram below. The table below covers all the possible digital I/O parameters. See Internal I/O Identifier (11.068) for details of which I/O is present for different I/O options. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 128 Short description Displays the state for digtial input/output 3 Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate 2ms write Display Format Standard Decimal Places Coding RO, ND, NC, PT Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 129 Displays the state for Safe Torque Off 1 input Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate 2ms write Display Format Standard Decimal Places Coding RO, ND, NC, PT See Digital I/O 01 State (08.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 130 08.013 Digital I/O 03 Invert Short description Set to invert Digital I/O 03 Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, TE Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 131 Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, TE Value Text Not Invert Invert See Digital I/O 01 Invert (08.011). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 132 Defines the source or destination parameter for Digital I/O 3 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 6.030 Units Type 16 Bit User Save Update Rate Drive Reset Read Display Format Standard Decimal Places Coding RW, DE, PT, BU Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 133 Short description Defines the polarity of the input logic Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, TE, BU Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 134 Displays the state for the Keypad Run Forward button Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate Background write Display Format Standard Decimal Places Coding RO, ND, NC, PT See Digital I/O 01 State (08.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 135 A value of 0 or 1 allows the input state to be non-inverted or inverted respectively. An additional toggle function is provided for Keypad Run button inputs. The toggle function output changes state on each rising edge (0 to 1 change) at its input. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 136 Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Drive Reset Read Display Format Standard Decimal Places Coding RW, DE, PT, BU See Digital I/O 01 Source/Destination (08.021). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 137 3. The corresponding Digital I/O Source/Destination parameter is not as valid source (e.g. 0.000) and the drive has been powered-up or reset since it was first selected. If the above conditions are not met, the digital output is controlled by the normal logic. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 138 (Display: 0000000000000000) (Display: 1111111111111111) Default Units (Display: 0000000000000000) Type 16 Bit Volatile Update Rate 250µs read Display Format Binary Decimal Places Coding RW, PT, BU See Digital I/O Output Enable Register 1 (08.071). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 139 Menu 9 Single Line Descriptions − User Functions 1 Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 140 Off (0) 09.063 Scope Mode Single (0), Normal (1), Auto (2) Single (0) 09.064 Scope Arm Off (0) or On (1) Off (0) 09.065 Scope Data Not Ready Off (0) or On (1) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 141 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 142 Menu 9 − User Functions 1 Mode: Open‑Loop Menu 9 provides the parameters for the following features: 1. Logic functions 2. Motorised Pot 3. Binary Sum 4. Timers 5. Scope function Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 143 1 until the input to the delay has been at 1 for the delay time. If Logic Function 1 Delay (09.009) or Logic Function 2 Delay (09.019) is negative then the output remains at 1 until the input to the delay has been 0 for the delay time. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 144 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 145 Motorised Pot Scaling (09.024) Motorised Pot Scaling (09.024) > 1.000 the output will exceed the range of the destination parameter, and so the destination parameter will be at its maximum or minimum before the output of the motorised pot reaches the limits of its range. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 146 If the maximum of the destination parameter > 7, Binary Sum Output (09.032) is routed in the same way as any other destination where the destination target is at its full scale value when the Binary Sum Output (09.032) = 7 + Binary Sum Offset (09.034). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 147 1. If Date/Time Selector (06.019) is changed and the drive is reset then the source for the timers will change, therefore Timer 1 Repeat Function Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 148 (09.039) and Timer 2 Repeat Function (09.049) are reset to 0 to disable the timers, and the date and time entries in the trip log are cleared. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 149 Units Type 16 Bit Power Down Save Update Rate 4ms write Display Format Standard Decimal Places Coding RO, ND, NC, PT Motorised Pot Output (09.003) shows the output of the motorised pot function. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 150 1 until the input to the delay has been at 1 for the delay time. If Logic Function 1 Delay (09.009) is negative then the output remains at 1 until the input to the delay has been 0 for the delay time. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 151 Defines input source 2 of logic function 2 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Drive reset read Display Format Standard Decimal Places Coding RW, PT, BU Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 152 1 until the input to the delay has been at 1 for the delay time. If Logic Function 2 Delay (09.019) is negative then the output remains at 1 until the input to the delay has been 0 for the delay time. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 153 Motorised Pot Scaling (09.024) Motorised Pot Scaling (09.024) > 1.000 the output will exceed the range of the destination parameter, and so the destination parameter will be at its maximum or minimum before the output of the motorised pot reaches the limits of its range. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 154 Set to add two to the binary sum output Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate 4ms read Display Format Standard Decimal Places Coding RW, NC See Binary Sum Output (09.032). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 155 Background read Display Format Date Decimal Places Coding Timer 1 Start Date (09.035) defines the start date within the repeat period of timer 1. See Timer 1 Repeat Function (09.039) for more information. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 156 Monday, etc.). If the stop time event is set to occur at or before the start time event or the Timer 1 Repeat Function (09.039) = 0 or Timer 1 Enable (09.040) = 0 the output remains inactive at all times (i.e. Timer 1 Output (09.042) = 0 if Timer 1 Invert (09.041) = 0). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 157 Defines the start date for timer 2 Mode Open‑Loop 311299 Minimum Maximum (Display: 00-00-00) (Display: 31-12-99) Default Units (Display: 00-00-00) Type 32 Bit User Save Update Rate Background read Display Format Date Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 158 Type 8 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, TE Value Text None Hour Week Month Year One off Minute See Timer 1 Repeat Function (09.039). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 159 Defines the source of scope trace 2 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Drive reset read Display Format Standard Decimal Places Coding RW, PT, BU Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 160 Defines the scope trigger threshold Mode Open‑Loop Minimum -2147483648 Maximum 2147483647 Default Units Type 32 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding See Scope Trigger Source (09.060). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 161 When the file transfer is complete, data acquisition begins again and Scope Data Not Ready (09.065) is set to 1 for a period that is long enough to fill the scope buffer with new data. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 162 The scope function can capture up to 4000 bytes of parameter data. The Scope Time Period (09.069) gives the length of the time period covered by the scope buffer in milliseconds which depends on the number of traces stored, the sample time and the size of the parameters used as trace sources. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 163 Short description Set to reset the scope auto-save function Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate Background read Display Format Standard Decimal Places Coding See Scope Auto-save Mode (09.070). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 164 Maximum Default Units Type 8 Bit Power Down Save Update Rate Background write Display Format Standard Decimal Places Coding RO, TE, NC Value Text Disabled Active Stopped Failed See Scope Auto-save Mode (09.070). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 165 Menu 10 Single Line Descriptions − Status and Trips Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 166 RO Time ND 10.061 Braking Resistor Resistance 0.00 to 10000.00 Ω 0.00 Ω RW Num 10.062 Low Load Detected Alarm Off (0) or On (1) 10.063 Local Keypad Battery Low Off (0) or On (1) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 167 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 168 Menu 10 − Status and Trips Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 169 Indicates that the drive is running below the set speed Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate Background write Display Format Standard Decimal Places Coding RO, ND, NC, PT See At Speed Lower Limit (03.006). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 170 RO, ND, NC, PT Braking IGBT Active (10.011) is set to one if the braking IGBT is active. As the braking IGBT active periods may be short, each time the braking IGBT is Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 171 Indicates that the motor overload accumulator is above 75% and the output current is high Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate Background write Display Format Standard Decimal Places Coding RO, ND, NC, PT Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 172 Default Units Type 8 Bit Power Down Save Update Rate Write on trip Display Format Standard Decimal Places Coding RO, TE, ND, NC, PT, BU Click here to view trips in numerical order. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 173 Encoder 12 Encoder 13 External Trip I/O Overload Inductance Inductor Too Hot Inter-connect Island Keypad Mode Line Sync Low Load Motor Too Hot Name Plate None OHt Brake OHt Control OHt dc bus Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 174 Reserved 238 Reserved 239 Reserved 240 Reserved 241 Reserved 242 Reserved 243 Reserved 244 Reserved 245 Reserved 246 Reset Reset Logs Resistance Slot1 Different Slot1 Error Slot1 HF Slot1 Not Fitted Slot1 Watchdog Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 175 User Trip 66 User Trip 67 User Trip 68 User Trip 69 User Trip 70 User Trip 71 User Trip 72 User Trip 73 User Trip 74 User Trip 75 User Trip 76 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 176 Voltage Range Watchdog Trip 0 (10.020) to Trip 9 (10.029) store the most recent 10 trips that have occurred where Trip 0 (10.020) is the most recent and Trip 9 (10.029) is the Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 177 All drive functions are stopped and the trip message will be displayed on the drive keypad. The error can only be reset by powering the drive down and up again. The table below gives the reasons for internal faults and their corresponding trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 178 6. Brake R Too Hot is active or the system has been set up to disable the braking IGBT based on the braking resistor temperature and the resistor is too hot (i.e. bit 2 of Action On Trip Detection (10.037) is set). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 179 Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit Power Down Save Update Rate Write on trip Display Format Standard Decimal Places Coding RO, TE, ND, NC, PT, BU See Trip 0 (10.020). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 180 Action On Trip Detection (10.037) = 0 and the accumulator reaches 100% an Brake R Too Hot trip is initiated. If bit 1 of Action On Trip Detection (10.037) = 1 and the accumulator reaches 100% the braking IGBT is disabled until the accumulator falls below 95.0%. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 181 If Number Of Auto-reset Attempts (10.034) = 6 the auto-reset counter is held at zero, and so there is no limit on the number of auto-reset attempts. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 182 Analog Input 1 (07.001) Analog Input 1 (07.001) Analog Input 1 (07.001) Analog Input 2 (07.002) Analog Input 2 (07.002) Analog Input 2 (07.002) Analog Input 3 (07.003) Analog Input 3 (07.003) Analog Input 3 (07.003) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 183 Above Set Speed (10.007) Rated Load Reached (10.008) Current Limit Active (10.009) Regenerating (10.010) Braking IGBT Active (10.011) Braking Resistor Alarm (10.012) Reverse Direction Commanded (10.013) Reverse Direction Running (10.014) Supply Loss (10.015) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 184 Shows the time at which trip 2 occurred Mode Open‑Loop 235959 Minimum Maximum (Display: 00:00:00) (Display: 23:59:59) Default Units Type 32 Bit Power Down Save Update Rate Write on trip Display Format Time Decimal Places Coding RO, ND, NC, PT Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 185 Minimum Maximum (Display: 00-00-00) (Display: 31-12-99) Default Units Type 32 Bit Power Down Save Update Rate Write on trip Display Format Date Decimal Places Coding RO, ND, NC, PT See Trip 0 (10.020). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 186 Shows the date at which trip 8 occurred Mode Open‑Loop 311299 Minimum Maximum (Display: 00-00-00) (Display: 31-12-99) Default Units Type 32 Bit Power Down Save Update Rate Write on trip Display Format Date Decimal Places Coding RO, ND, NC, PT Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 187 RO, ND, NC, PT Local Keypad Battery Low (10.063) is set to one when a keypad is fitted to the front of the drive with an internal real-time clock and the battery is not Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 188 RO, ND, NC, PT The bits in Additional Status Bits (10.069) mirror the status bits parameters as shown below. Where the parameters do not exist in any mode the bit remains at zero. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 189 Mode Open‑Loop Minimum Maximum 65535 Default Units Type 16 Bit Power Down Save Update Rate Write on trip Display Format Standard Decimal Places Coding RO, ND, NC, PT, BU See Trip 0 (10.020). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 190 It is possible for some trips to cause the motor to stop before the trip is initiated (see Action On Trip Detection (10.037)). During the period while the motor is being stopped before the trip is initiated Stop Motor (10.080) is set to one. Once the motor stops Stop Motor (10.080) is set back to zero. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 191 Decimal Places Coding RO, ND, NC, PT When a trip occurs the time in milliseconds since the drive powered up is stored in Trip Time Identifier (10.103). The time rolls-over when it reaches Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 192 The bits in Potential Drive Damage Conditions (10.106) are set under the conditions shown in the table below to indicate that the user has put the drive in a condition that could potentially damage the drive. The bits in this parameter cannot be cleared by users. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 193 Auto-tune State (10.107) is zero unless an auto-tune is active when it shows the current state of the auto-tune sequence as follows: Parameter value Auto-tune state Stator resistance measurement Transient inductance measurement Stator inductance measurement Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 194 Menu 11 Single Line Descriptions − Miscellaneous Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 195 11.065 Drive Rating And Configuration 00000000 to 99999999 RO Num ND NC PT 11.066 Power Stage Identifier 0 to 255 RO Num ND NC PT 11.067 Control Board Identifier 0.000 to 65.535 RO Num ND NC PT Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 196 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 197 The rating dependent parameters are left at their default values. After the parameters have been transferred and saved to non-volatile memory a Card Rating trip is given as a warning. The table below gives a list of the rating dependent parameters. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 198 M2 No-load Lq (21.041) Rated Load Lq (05.069) M2 Rated Load Lq (21.042) No-load Phase Offset (05.070) M2 No-load Phase Offset (21.043) Rated Load Phase Offset (05.071) M2 Rated Load Phase Offset (21.044) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 199 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter Displayed At Power-up (11.022). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 200 Serial Address (11.023) defines the node address for the serial comms interface in the range from 1 to 247. Changing the parameters does not immediately change the serial communications settings. See Reset Serial Communications (11.020) for more details. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 201 Defines the serial baud rate of the drive Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit User Save Update Rate Read on serial communications reset Display Format Standard Decimal Places Coding RW, TE Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 202 Displays the drive derivative identifier Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit Volatile Update Rate Power-up write Display Format Standard Decimal Places Coding RO, ND, NC, PT, BU Drive Derivative (11.028) shows the derivative identifier. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 203 8 Bit Volatile Update Rate Power-up write Display Format Standard Decimal Places Coding RO, TE, ND, NC, PT Value Text 200V 400V 575V 690V Drive Rated Voltage (11.033) shows the voltage rating of the drive. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 204 NV media card or a value of 0. When NV Media Card File Number (11.037) corresponds to the number of a file the following data about the file is shown. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 205 NV Media Card File Checksum (11.040) shows the checksum from the file selected with NV Media Card File Number (11.037). If the media fileis a Unidrive SP SMARTCARD file, the checksum is (∑ All bytes except the checksum) modulo 65536. If the file was generated by a Unidrive M, a value of zero will be displayed. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 206 Defines which defaults are to be loaded into the drive Mode Open‑Loop Minimum Maximum Default Units Type 8 Bit Volatile Update Rate Background read Display Format Standard Decimal Places Coding RW, TE, NC Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 207 If the security code entered must be correct for the keypad state machine to switch to the Parameter view mode. It is then possible to access all parameters normally. Security can be cleared as follows: Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 208 Onboard User Program: Status (11.048) shows the status of the onboard user program. Value Description A user program is present but is stopped The user program is running The user program has an exception No user program is present Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 209 Shows the most significant 9 decimal digits of the drive serial number Mode Open‑Loop Minimum Maximum 999999999 Default Units Type 32 Bit Volatile Update Rate Power-up write Display Format Standard Decimal Places Coding RO, ND, NC, PT See Serial Number LS (11.052). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 210 Option Slot Identifiers (11.056) is a volatile parameter its value is saved in non-volatile memory when parameters are saved. If Option Slot Identifiers (11.056) is changed the drive must be powered down and then powered up again for the change to take effect. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 211 Displays the product identifier characters Mode Open‑Loop Minimum 1177759792 Maximum 2147483647 Default Units Type 32 Bit Volatile Update Rate Power-up write Display Format String Decimal Places Coding RO, ND, NC, PT Background Read Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 212 Analog and digital I/O Digtial only I/O Analogue and digital I/O with additional relay Servo drive I/O The tables below show which I/O functions are available for each of the internally fitted I/O options. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 213 Defaults for all menus are loaded when the most significant digit of Core Parameter Database Version (11.070) changes. Therefore if the drive firmware is modified and the most significant digit of the core database version has changed an EEPROM Fail.001 trip is initiated and default parameters are loaded. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 214 Update Rate Background write Display Format Standard Decimal Places Coding RO, ND, NC, PT NV Media Card Warning Suppression Flag (11.076) shows the state of the warning flag for the currently fitted card. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 215 Defines characters 13-16 of a string which can be used to identify the drive Mode Open‑Loop Minimum -2147483648 Maximum 2147483647 Default Units Type 32 Bit User Save Update Rate Display Format String Decimal Places Coding RW, PT See Drive Name Characters 1-4 (11.079). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 216 Keypad Port Serial Address (11.090) defines the node address for the keypad port serial comms interface. Normally the default value of 1 is used, but this can be changed if required. The keypad attached to the port will sense the address automatically. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 217 If there are less external rectifiers than defined by Number Of Rectifiers Expected (11.096) then a Configuration is initiated with the sub-trip indicating how many rectifers should be present. See Trip 0 (10.020). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 218 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 219 Displays the output of threshold detector 1 Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit Volatile Update Rate 4ms write Display Format Standard Decimal Places Coding RO, ND, NC, PT See Threshold Detector 1 Output (12.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 220 The variable selector functions are always active even if the source and destination are not routed to valid parameters. If a source is not a valid parameter then the source value is taken as 0. The update rate for each of the variable selector functions is always 4ms. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 221 The sectional control function is intended to apply scaling and a speed offset to a 16 bit position value to generate a new 16 bit position value. The output can be used as an input to the Standard motion controller (Menu 13) and to generate an encoder simulation output (Menu 3). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 222 (13.021) in the standard motion controller which is used to provide the speed reference and to control the local motor attached to the drive. The encoder simulation system is used to generate the section output to be fed into the next drive. The source for the encoder simulation is Standard Motion Local Reference Position (13.021). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 223 Defines the scaling for the 1st input for variable selector 1 Mode Open‑Loop Minimum -4.000 Maximum 4.000 Default 1.000 Units Type 16 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding See Variable Selector 1 Source 1 (12.008). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 224 Defines the hysteresis for threshold detector 2 Mode Open‑Loop Minimum 0.00 Maximum 25.00 Default 0.00 Units Type 16 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding See Threshold Detector 1 Output (12.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 225 Update Rate Background read Display Format Standard Decimal Places Coding RW, TE Value Text Input 1 Input 2 Subtract Multiply Divide Time Const Ramp Modulus Powers Sectional See Variable Selector 1 Source 1 (12.008). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 226 Enables variable selector 2 Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding RW, BU See Variable Selector 1 Source 1 (12.008). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 227 Menu 14 Single Line Descriptions − User PID Controller Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 228 Min Error (6), Max Error (7) 14.060 PID1 Feedback Square Root Enable 1 Off (0) or On (1) Off (0) 14.061 PID2 Feedback Square Root Enable Off (0) or On (1) Off (0) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 229 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 230 In the following sections a description is given for PID controller 1. The descriptions also apply to PID controller 2 except where stated. The sample rate for the PID controllers is always 4ms. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 231 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 232 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 233 PID1 Output Scaling (14.015) can be used to scale the output, which is limited to a range from -100.00% to 100.00% after this function. The output is then added to PID1 Feed-forwards Reference (14.019) and is again limited to the range from -100.00% to 100.00% before being routed to the destination defined by PID1 Destination (14.016). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 234 It is easier to use a pressure transducer than a flow transducer, and so the feedback from the transducer needs to be converted from pressure to flow. As flow = Constant x √Pressure the square root function can be used in the conversion. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 235 Defines the Kp gain used for PID1 Mode Open‑Loop Minimum 0.000 Maximum 4.000 Default 1.000 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding See PID1 Output (14.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 236 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Drive reset read Display Format Standard Decimal Places Coding RW, DE, PT, BU See PID1 Output (14.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 237 Displays the value of the error for PID1 Mode Open‑Loop Minimum -100.00 Maximum 100.00 Default Units Type 16 Bit Volatile Update Rate 4ms write Display Format Standard Decimal Places Coding RO, ND, NC, PT See PID1 Output (14.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 238 Defines the level of the pre-sleep boost function Mode Open‑Loop Minimum 0.00 Maximum 100.00 Default 0.00 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding See PID1 Reference Source (14.003). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 239 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Drive reset read Display Format Standard Decimal Places Coding RW, PT, BU See PID1 Feedback Source (14.004). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 240 Defines the Kp gain used for PID2 Mode Open‑Loop Minimum 0.000 Maximum 4.000 Default 1.000 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding See PID1 Proportional Gain (14.010). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 241 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Drive reset read Display Format Standard Decimal Places Coding RW, DE, PT, BU See PID1 Destination (14.016). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 242 Displays the value of the error for PID2 Mode Open‑Loop Minimum -100.00 Maximum 100.00 Default Units Type 16 Bit Volatile Update Rate 4ms write Display Format Standard Decimal Places Coding RO, ND, NC, PT See PID1 Error (14.022). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 243 The description given in PID1 Output (14.001) assumed that PID1 Mode Selector (14.059) = 0 so that PID controller 1 uses its own feedback (FBK1). It is possible to select alternative configurations that allow various combinations of feedback or error from either PID controller to be used as shown below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 244 Enables the squre root function of PID2 Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding See PID1 Feedback Square Root Enable 1 (14.060) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 245 Enables the squre root function of PID1 Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate 4ms read Display Format Standard Decimal Places Coding See PID1 Feedback Output Scaling (14.058). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 246 -2147483648 to 2147483647 RW Num 18.053 Application Menu 1 Power‑down Save Long Integer 53 -2147483648 to 2147483647 RW Num 18.054 Application Menu 1 Power‑down Save Long Integer 54 -2147483648 to 2147483647 RW Num Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 247 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 248 18.005 Application Menu 1 Read-only Integer 5 Short description General read-only integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit Volatile Update Rate Display Format Standard Decimal Places Coding RO, PR, ND, NC Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 249 18.012 Application Menu 1 Read-write Integer 12 Short description General read-write integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 250 18.019 Application Menu 1 Read-write Integer 19 Short description General read-write integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 251 18.026 Application Menu 1 Read-write Integer 26 Short description General read-write integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 252 18.033 Application Menu 1 Read-write bit 33 Short description General read-write bit application parameter Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 253 18.040 Application Menu 1 Read-write bit 40 Short description General read-write bit application parameter Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 254 18.047 Application Menu 1 Read-write bit 47 Short description General read-write bit application parameter Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 255 18.054 Application Menu 1 Power-down Save Long Integer 54 Short description General power-down save long integer application parameter Mode Open‑Loop Minimum -2147483648 Maximum 2147483647 Default Units Type 32 Bit Power Down Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 256 -2147483648 to 2147483647 RW Num 19.053 Application Menu 2 Power‑down Save Long Integer 53 -2147483648 to 2147483647 RW Num 19.054 Application Menu 2 Power‑down Save Long Integer 54 -2147483648 to 2147483647 RW Num Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 257 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 258 19.006 Application Menu 2 Read-only Integer 6 Short description General read-only integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit Volatile Update Rate Display Format Standard Decimal Places Coding RO, PR, ND, NC Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 259 19.013 Application Menu 2 Read-write Integer 13 Short description General read-write integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 260 19.020 Application Menu 2 Read-write Integer 20 Short description General read-write integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 261 19.027 Application Menu 2 Read-write Integer 27 Short description General read-write integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 262 19.034 Application Menu 2 Read-write bit 34 Short description General read-write bit application parameter Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 263 19.041 Application Menu 2 Read-write bit 41 Short description General read-write bit application parameter Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 264 19.048 Application Menu 2 Read-write bit 48 Short description General read-write bit application parameter Mode Open‑Loop Minimum Maximum Default Units Type 1 Bit User Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 265 19.054 Application Menu 2 Power-down Save Long Integer 54 Short description General power-down save long integer application parameter Mode Open‑Loop Minimum -2147483648 Maximum 2147483647 Default Units Type 32 Bit Power Down Save Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 266 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 267 20.006 Application Menu 3 Read-write Integer 6 Short description General read-write integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit Volatile Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 268 20.013 Application Menu 3 Read-write Integer 13 Short description General read-write integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit Volatile Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 269 20.020 Application Menu 3 Read-write Integer 20 Short description General read-write integer application parameter Mode Open‑Loop Minimum -32768 Maximum 32767 Default Units Type 16 Bit Volatile Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 270 20.027 Application Menu 3 Read-write Long Integer 27 Short description General read-write long integer application parameter Mode Open‑Loop Minimum -2147483648 Maximum 2147483647 Default Units Type 32 Bit Volatile Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 271 20.034 Application Menu 3 Read-write Long Integer 34 Short description General read-write long integer application parameter Mode Open‑Loop Minimum -2147483648 Maximum 2147483647 Default Units Type 32 Bit Volatile Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 272 20.040 Application Menu 3 Read-write Long Integer 40 Short description General read-write long integer application parameter Mode Open‑Loop Minimum -2147483648 Maximum 2147483647 Default Units Type 32 Bit Volatile Update Rate Display Format Standard Decimal Places Coding Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 273 Menu 22 Single Line Descriptions − Menu 0 Set-up Mode: Open‑Loop Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 274 0.000 22.060 Parameter 00.060 Set‑up 0.000 to 59.999 0.000 22.061 Parameter 00.061 Set‑up 0.000 to 59.999 0.000 22.062 Parameter 00.062 Set‑up 0.000 to 59.999 0.000 22.063 Parameter 00.063 Set‑up 0.000 to 59.999 0.000 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 275 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 276 Defines the parameter to be shown in 00.005 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 1.014 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 277 Defines the parameter to be shown in 00.011 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 5.001 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 278 Defines the parameter to be shown in 00.017 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 8.026 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 279 Defines the parameter to be shown in 00.023 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 1.005 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 280 Defines the parameter to be shown in 00.029 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 11.036 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 281 Defines the parameter to be shown in 00.035 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 11.024 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 282 Defines the parameter to be shown in 00.041 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 5.018 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 283 Defines the parameter to be shown in 00.047 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 5.006 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 284 Maximum 59.999 Default See exceptions below Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU Region Default Value 50Hz 0.000 60Hz 4.015 4.015 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 285 Defines the parameter to be shown in 00.059 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 286 Defines the parameter to be shown in 00.065 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 287 Defines the parameter to be shown in 00.071 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 288 Defines the parameter to be shown in 00.077 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 289 Defines the parameter to be shown in 00.080 Mode Open‑Loop Minimum 0.000 Maximum 59.999 Default 0.000 Units Type 16 Bit User Save Update Rate Background read Display Format Standard Decimal Places Coding RW, PT, BU See Parameter 00.001 Set-up (22.001). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 290 IP IP address Mac MAC address Ver Version number SMP Slot, menu, parameter Num Number parameter DE Destination RA Rating dependent NC Non-copyable PT Protected default value Power- FI Filtered US User save down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 291 If LSRPM Motor Set-up Enable (29.200) is set to Off (0), then the LSRPM motor set-up detailed above is disabled. LSRPM Motor Set-up Enable (29.200) should be set to Off (0) if the drive is required to control a non-LSRPM permanent magnet motor. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 292 The error can only be reset by powering the drive down and up again. The table below gives the reasons for internal faults and their corresponding trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 293 6. Brake R Too Hot is active or the system has been set up to disable the braking IGBT based on the braking resistor temperature and the resistor is too hot (i.e. bit 2 of Action On Trip Detection (10.037) is set). Trips Summary (numerical order) Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 294 User Trip 58 User Trip 59 User Trip 60 User Trip 61 User Trip 62 User Trip 63 User Trip 64 User Trip 65 User Trip 66 User Trip 67 User Trip 68 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 295 User Trip 128 User Trip 129 User Trip 130 User Trip 131 User Trip 132 User Trip 133 User Trip 134 User Trip 135 User Trip 136 User Trip 137 User Trip 138 Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 296 Encoder 6 Encoder 7 Encoder 8 Encoder 9 Phasing Error Destination Slot1 HF Slot1 Watchdog Slot1 Error Slot1 Not Fitted Slot1 Different Slot2 HF Slot2 Watchdog Slot2 Error Slot2 Not Fitted Slot2 Different Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 297 Indicates that a current loss was detected in current mode on Analog Input 2 (Terminal 7). In 4-20mA and 20-4mA modes. loss of input is detected if the current falls below 3mA. See Analog Input 2 Mode (07.011) for further details. Recommended actions: Check control wiring is correct. Check control wiring is undamaged. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 298 Ensure that the motor is stationary before the drive is enabled. zero speed threshold. Trip Autotune 2 Value Short description The drive has tripped during a rotating auto-tune. The cause of the trip can be identified from the associated sub-trip number. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 299 An Autotune 7 trip is initiated during a rotating auto-tune, if the number of motor poles or the position feedback resolution have been set up incorrectly where position feedback is being used. Recommeded actions: Check the lines per revolution for the feedback device. Check the number of poles in Number Of Motor Poles (05.011). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 300 An attempt has been made to access a file on a NV media card, but the file is already being accessed be an Option Module, such as one of the Applications modules. No data is transferred. Recommended actions: Wait for the Option Module to finish accessing the NV media card and re-attempt the required function. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 301 Card No Data Value Short description An attempt has been made to access a non-existent file on a NV media card. No data is transferred. Recommended actions: Ensure data block number is correct. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 302 Error in option slot 1 Error in option slot 2 Error in option slot 3 Error in option slot 4 Recommended actions: Ensure the source / destination option module is installed on the correct slot. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 303 Reason for trip There should be a derivative image in the product but this has been erased. The identifer is out of range. The derivative image has been changed. Trip Derivative Image Value Short description Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 304 An error has been detected in the derivative product image. The sub-trip indicated the reason for the trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 305 The option module fitted in slot 3 is not allowed As 30. with the derivative image. The option module fitted in slot 4 is not allowed As 30. with the derivative image. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 306 Ensure the drive is programmed to the latest software version. Hardware fault - return drive to supplier. Trip EEPROM Fail Value Short description EEPROM Fail trip indicates that default parameters have been loaded because of the reasons given below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 307 SC SC device single turn sine wave commutation signals. SC SC device marker This trip can occur if the position feedback device type selected in P1 Device Type (03.038) is not correct for the position feedback device connected to the drive. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 308 This trip indicates that the encoder has indicated an error or that the power supply has failed to an SSI encoder. This trip can also indicate a wire break to an SSI encoder. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 309 This trip indicates that the data read from the encoder was out of range during auto-configuration. No parameters will be modified with data read from the encoder as a result of auto-configuration. The tens in the sub-trip number indicate the interface number (i.e. 1 for P1 interface and 2 for P2 interface). Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 310 When half of Rated Current (05.007) is applied in the d axis of the motor in each direction the inductance must change by at least (K / (2 x Full Scale Current Kc (11.061))) H. The specific reasons for each of the sub-trips are given in the table below. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 311 This trip indicates a motor thermal overload based on the Rated Current (05.007) and Motor Thermal Time Constant 1 (04.015). Motor Protection Accumulator (04.019) displays the motor temperature as a percentage of the maximum value. The drive will trip on Motor Too Hot when Motor Protection Accumulator (04.019) gets to 100%. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 312 03: I/O board thermistor system Recommended actions: Check enclosure / drive fans are still functioning correctly. Check enclosure ventilation paths. Check enclosure door filters. Increase ventilation. Reduce the drive switching frequency. Check ambient temperature. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 313 Decrease acceleration / deceleration rates. Reduce motor load. Check DC bus ripple. Ensure all three input phases are present and balanced. Recommended actions with sub-trip 300: Reduce the braking load. Trip OHt Power Value Short description Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 314 If seen during auto-tune reduce the voltage boost. Check for short circuit on the output cabling. Check integrity of the motor insulation using a Megger. Check feedback device wiring. Check feedback drive mechanical coupling. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 315 During drive mode changeover option modules must acknowledge that they have stopped accessing the communications system between the option slots and the drive. If an option module does not do this in the allowed time then this trip is produced. Recommended actions: Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 316 Decrease the braking resistor value (staying above the minimum value). Check nominal AC supply level. Check for supply disturbances which could cause the DC bus level to rise. Check motor insulation using a Megger. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 317 *For a parallel power-module system the rectifier number will be one as it is not possible to determine which rectifier has detected the fault. Recommended actions: Hardware fault - contact the supplier of the drive. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 318 00: Rectifier internal power supply overload. number number* *For a parallel power-module system the rectifier number will be zero as it is not possible to determine which rectifier has detected the fault. Recommended actions: Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 319 Trip Reserved 104 Value Short description Reserved trip number. Trip Reserved 105 Value Short description Reserved trip number. Trip Reserved 106 Value Short description Reserved trip number. Trip Reserved 107 Value Short description Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 320 If this trip occurs please consult the drive supplier. Trip Reserved 228 Value Short description If this trip occurs please consult the drive supplier. Trip Reserved 229 Value Short description Reserved trip number. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 321 Value Short description Reserved trip number. Trip Reserved 240 Value Short description Reserved trip number. Trip Reserved 241 Value Short description Reserved trip number. Trip Reserved 242 Value Short description Reserved trip number. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 322 Slot3 Different then Slot4 Different. Drive user parameters must be saved to prevent this trip on the next power-up if the module has changed. If the menus have been changed, but not the module, the trip will not occur on the next power-up. The sub-trip number gives the following indications of the reason for the trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 323 The drive failed to upload menu tables from the module and timed-out (5s). Menu table CRC invalid. Recommended actions: Ensure the option module is installed correctly. Replace the option module. Replace the drive. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 324 This trip indicates that there is a fault with the option module in option slot 2 that means that this module cannot operate. The possible causes of the trip are given by the sub-trip value. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 325 Slot3 Different then Slot4 Different. Drive user parameters must be saved to prevent this trip on the next power-up if the module has changed. If the menus have been changed, but not the module, the trip will not occur on the next power-up. The sub-trip number gives the following indications of the reason for the trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 326 The drive failed to upload menu tables from the module and timed-out (5s). Menu table CRC invalid. Recommended actions: Ensure the option module is installed correctly. Replace the option module. Replace the drive. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 327 This trip indicates that there is a fault with the option module in option slot 4 that means that this module cannot operate. The possible causes of the trip are given by the sub-trip value. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 328 This trip indicates that the soft start relay in the drive has failed to close or the soft start monitoring circuit has failed. Recommended actions: Hardware fault - contact the supplier of the drive. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 329 Parameter size Value 1 bit 8 bit 16 bit 32 bit 64 bit Parameter type Value Volatile User save Power-down save Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 330 This trip indicates that a temperature sensor connected to an analogue input or terminal 15 on the position feedback interface has a low impedance (i.e. < 50 Ohms). The cause of the trip can be identified by the sub-trip number. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 331 Short description This trip can be initiated from within an onboard user program using a function call which defines the sub-trip number. Recommended actions: Check the user program. Trip User Program Value Short description Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 332 An error has been detected in the onboard user program image. The sub-trip indicated the reason for the trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 333 *Image is not compatible with the control board serial As 80. number Image has detected and prevented attempted pointer access outside of the IEC task’s heap area. Image has detected and prevented misaligned pointer usage. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 334 Perform a user save in Pr mm.000 to ensure that the trip doesn't occur the next time the drive is powered up. Ensure that the drive has enough time to complete the save before removing the power to the drive. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 335 This trip is not used by the drive and can be used for a user trip. Trip User Trip 52 Value Short description This trip is not used by the drive and can be used for a user trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 336 This trip is not used by the drive and can be used for a user trip. Trip User Trip 65 Value Short description This trip is not used by the drive and can be used for a user trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 337 This trip is not used by the drive and can be used for a user trip. Trip User Trip 78 Value Short description This trip is not used by the drive and can be used for a user trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 338 This trip is not used by the drive and can be used for a user trip. Trip User Trip 113 Value Short description This trip is not used by the drive and can be used for a user trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 339 This trip is not used by the drive and can be used for a user trip. Trip User Trip 126 Value Short description This trip is not used by the drive and can be used for a user trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 340 This trip is not used by the drive and can be used for a user trip. Trip User Trip 139 Value Short description This trip is not used by the drive and can be used for a user trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 341 This trip is not used by the drive and can be used for a user trip. Trip User Trip 152 Value Short description This trip is not used by the drive and can be used for a user trip. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...
  • Page 342 Reduce the level of supply disturbance. Set Regen Maximum Voltage to zero to disable this trip. Trip Watchdog Value Short description This trip indicates that the control word watchdog has been enabled and has timed out. Powerdrive F300 Parameter Reference Guide Issue: 01.15.00...