Internal / Hardware trips

Trips {HF01} to {HF20} are internal faults that do not have trip numbers.
If one of these trips occurs, the main drive processor has detected an
irrecoverable error. All drive functions are stopped and the trip message
will be displayed on the drive keypad. If a non permanent trip occurs this
may be reset by power cycling the drive. On power up after it has been
power cycled the drive will trip on Stored HF. Enter 1299 in mm.000 to
clear the Stored HF trip.
13.6
Alarm indications
In any mode, an alarm is an indication given on the display by alternating
the alarm string with the drive status string on the first row and showing
the alarm symbol in the last character in the first row. If an action is not
taken to eliminate any alarm except "Auto Tune and Limit Switch" the
drive may eventually trip. Alarms are not displayed when a parameter is
being edited, but the user will still see the alarm character on the upper
row.
Table 13-6 Alarm indications
Alarm string
Motor Protection Accumulator (04.019) in the drive
Motor Overload
has reached 75.0 % of the value at which the drive
will trip and the load on the drive is >100 %.
Drive over temperature. Percentage Of Drive
Drive Overload
Thermal Trip Level (07.036) in the drive is greater
than 90 %.
The autotune procedure has been initialized and an
Auto Tune
autotune in progress.
13.7

Status indications

Table 13-7 Status indications
Upper row
string
The drive is inhibited and cannot be run.
The Safe Torque Off signal is not applied to
Inhibit
Safe Torque Off terminals or Pr 06.015 is
set to 0
The drive is ready to run. The drive enable
Ready
is active, but the drive inverter is not active
because the final drive run is not active
Stop
The drive is stopped / holding zero speed.
Run
The drive is active and running
Supply Loss
Supply loss condition has been detected
The motor is being decelerated to zero
Deceleration
speed / frequency because the final drive
run has been deactivated.
dc injection
The drive is applying dc injection braking
The drive has tripped and no longer
Trip
controlling the motor. The trip code
appears in the lower display
Under
The drive is in the under voltage state
Voltage
either in low voltage or high voltage mode
Heat
The motor pre-heat functions inactive
The drive is performing a 'phasing test on
Phasing
enable'.
282
Electrical
Getting
Basic
installation
started
parameters
the motor
Description
Description
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Running
NV Media Card
Optimization
Operation
Table 13-8 Option module and NV Media Card and other status
indications at power-up
First row
Second row string
string
Booting
Drive parameters are being loaded from a NV Media Card
Booting
User program is being loaded from a NV Media Card to the drive
Booting
User program is being loaded from a NV Media Card to the option
module in slot X
Writing To
Data is being written to a NV Media Card to ensure that its copy of the
drive parameters is correct because the drive is in Auto or Boot mode
Waiting For
The drive is waiting for the processor in the power stage to respond
after power-up
Waiting For
The drive is waiting for the Options Modules to respond after power-up
Uploading
From
At power-up it may be necessary to update the parameter database
held by the drive because an option module has changed or because
an applications module has requested changes to the parameter
Drive
structure. This may involve data transfer between the drive an option
output
modules. During this period 'Uploading From Options' is displayed
stage
13.8

Programming error indications

Following are the error message displayed on the drive keypad when an
error occurs during programming of drive firmware.
Table 13-9 Programming error indications
Error
String
There is not enough drive
Error 1
memory requested by all
the option modules.
At least one option module
Error 2
did not acknowledge the
reset request.
The boot loader failed to
Error 3
erase the processor flash
The boot loader failed to
Error 4
program the processor
flash
One option module did not
initialize correctly. Option
Error 5
module did not set Ready
to Run flag.
Onboard
Advanced
Technical
PLC
parameters
data
Parameters
Parameters are being loaded
User Program
User program being loaded
Option
User program being loaded
Program
Data being written to NV Media
NV Card
Card
Power System
Waiting for power stage
Options
Waiting for an option module
Options
Loading parameter database
Reason
Power down drive and remove
some of the option modules
until the message disappears.
Power cycle drive
Power cycle drive and try
again. If problem persists,
return drive
Power cycle drive and try
again. If problem persists,
return drive
Remove faulty option module.