3.6.2

Enclosure layout

Please observe the clearances in the diagram below taking into account any appropriate notes for other devices / auxiliary equipment when planning
the installation.
Figure 3-34 Enclosure layout (size 3 to 8)
NOTE
For EMC compliance:
1. When using an external EMC filter, one filter is required for each drive.
2. Power cabling must be at least 100 mm (4 in) from the drive in all directions
Table 3-5 Spacing required between drive / enclosure and drive / EMC filter (size 3 to 8)
Drive Size
3
4
5
6
7
8
Powerdrive F300 User Guide
Issue Number: 2
Electrical
Getting
Basic
installation
started
parameters
the motor
AC supply
contactor and
fuses or MCB
Locate as
required
Ensure minimum clearances
are maintained for the drive
and external EMC filter. Forced
or convection air-flow must not
be restricted by any object or
cabling
The external EMC filter can be
bookcase mounted (next to the
drive) or footprint mounted (with
the drive mounted onto the filter).
External
controller
Signal cables
Plan for all signal cables
to be routed at least
300 mm (12 in) from the
drive and any power cable
Running
NV Media Card
Optimization
Operation
Enclosure
≥100mm
B
Spacing (B)
0 mm (0.00 in)
30 mm (1.18 in)
Onboard
Advanced
Technical
PLC
parameters
data
(4in)
B
≥100 mm
(4 in)
UL listing
Diagnostics
information
47