Example
To calculate the size of an enclosure for the following:
Three drives operating at the Normal Duty rating
External EMC filter for each drive
Braking resistors are to be mounted outside the enclosure
Maximum ambient temperature inside the enclosure: 40 °C
Maximum ambient temperature outside the enclosure: 30 °C
For example, dissipation of each drive: 101 W and dissipation of each
external EMC filter: 6.9 W (max).
Total dissipation: 3 x (101 + 6.9) = 323.7 W
Insert the following values:
40 °C
T
int
30 °C
T
ext
k
1.3
P
323.7 W
Then:
×
×
3
1.3
323.7
V
-------------------------------------- -
=
40 30
3
3
= 126.2 m
/hr (74.5 ft
3.7
Enclosure design and drive ambient
temperature
Drive derating is required for operation in high ambient temperatures
Totally enclosing or through panel mounting the drive in either a sealed
cabinet (no airflow) or in a well ventilated cabinet makes a significant
difference on drive cooling.
The chosen method affects the ambient temperature value (T
should be used for any necessary derating to ensure sufficient cooling
for the whole of the drive.
The ambient temperature for the four different combinations is defined
below:
1. Totally enclosed with no air flow (<2 m/s) over the drive
T
= T
+ 5 °C
rate
int
2. Totally enclosed with air flow (>2 m/s) over the drive
T
= T
rate
int
3. Through panel mounted with no airflow (<2 m/s) over the drive
T
= the greater of T
+5 °C, or T
rate
ext
4. Through panel mounted with air flow (>2 m/s) over the drive
T
= the greater of T
or T
rate
ext
Where:
T
= Temperature outside the cabinet
ext
T
= Temperature inside the cabinet
int
T
= Temperature used to select current rating from tables in
rate
Chapter 12 Technical data on page 232.
3.8

Heatsink fan operation

The drive is ventilated by an internal heatsink mounted fan. The fan
housing forms a baffle plate, channelling the air through the heatsink
chamber. Thus, regardless of mounting method (surface mounting or
through-panel mounting), the installing of additional baffle plates is not
required.
Ensure the minimum clearances around the drive are maintained to
allow air to flow freely.
The heatsink fan on all sizes is a variable speed fan. The drive controls
the speed at which the fan runs based on the temperature of the
heatsink and the drive's thermal model system. The maximum speed at
which the fan operates can be limited in Pr 06.045. This could incur an
output current derating. Refer to section 3.13.2 Fan removal
procedure on page 67 for information on fan removal. Size 6 to 11 are
also installed with a variable speed fan to ventilate the capacitor bank.
50
Electrical
Getting
Basic
installation
started
parameters
3
3
/min) (1 m
/ hr = 0.59 ft
/min)
rate
int
int
Running
NV Media Card
Optimization
the motor
Operation
3.9
Enclosing standard drive for high
environmental protection
An explanation of environmental protection rating is provided in section
12.1.9 IP / UL Rating .
The standard drive is rated to IP20 pollution degree 2 (dry, non-
conductive contamination only) (NEMA 1). However, it is possible to
configure the drive to achieve IP65 rating (sizes 3 to 8) or IP54 (size 9,
10 and 11) (NEMA 12) at the rear of the heatsink for through-panel
mounting (some current derating is required). Refer to section
12.1.1 Power and current ratings (Derating for switching frequency and
temperature) on page 232.
This allows the front of the drive, along with various switchgear, to be
housed in a high IP enclosure with the heatsink protruding through the
panel to the external environment. Thus, the majority of the heat
generated by the drive is dissipated outside the enclosure maintaining a
reduced temperature inside the enclosure. This also relies on a good
seal being made between the heatsink and the rear of the enclosure
using the gaskets provided.
Figure 3-37 Example of IP65 (sizes 3 to 8) layout
IP65 (sizes 3 to 8)
) which
IP20
(NEMA1)
The main gasket should be installed as shown in Figure 3-38.
On drive sizes 3, 4 and 5, in order to achieve the high IP rating at the
rear of the heatsink it is necessary to seal a heatsink vent by installing
the high IP insert as shown in Figure 3-40, Figure 3-41 and Figure 3-42.
Onboard
Advanced
Technical
PLC
parameters
data
enclosure
Gasket
seal
Powerdrive F300 User Guide