Advanced Menus; Display Messages; Advanced Menu Descriptions; Ki-Keypad Set-Up Parameters - Emerson Powerdrive F300 User Manual

Universal variable speed ac drive for induction and permanent magnet motors
Hide thumbs Also See for Powerdrive F300:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
5.5

Advanced menus

The advanced menus consist of groups or parameters appropriate to a
specific function or feature of the drive. Menus 0 to 41 can be viewed on
the KI-HOA Keypad RTC.
The option module menus (S.mm.ppp) are only displayed if option
modules are installed. Where S signifies the option module slot number
and the mm.ppp signifies the menu and parameter number of the option
module's internal menus and parameter.
Table 5-5 Advanced menu descriptions
Menu
Commonly used basic set up parameters for quick / easy
0
programming
1
Frequency / Speed reference
2
Ramps
3
Frequency slaving, speed feedback and speed control
4
Torque and current control
5
Motor control
6
Sequencer and clock
7
Analog I/O, Temperature monitoring
8
Digital I/O
Programmable logic, motorized pot, binary sum, timers and
9
scope
10
Status and trips
11
Drive set-up and identification, serial communications
12
Threshold detectors and variable selectors
14
User PID controller
15
Option module slot 1 set-up menu
16
Option module slot 2 set-up menu
17
Option module slot 3 set-up menu
18
General option module application menu 1
19
General option module application menu 2
20
General option module application menu 3
22
Menu 0 set-up
23
Not allocated
28
Reserved menu
29
Pumping functions
30
Onboard user programming application menu
Slot 1
Slot 1 option menus*
Slot 2
Slot 2 option menus*
Slot 3
Slot 3 option menus*
*Only displayed when the option modules are installed.
5.5.1
KI-HOA Keypad RTC
To enter the keypad set-up menu press and hold the escape
button on the keypad from status mode. All the keypad parameters are
saved to the keypad non-volatile memory when exiting from the keypad
set-up menu.
To exit from the keypad set-up menu press the escape
button. Below are the keypad set-up parameters.
Powerdrive F300 User Guide
Issue Number: 2
Electrical
Getting
Basic
installation
started
parameters
the motor
Description
or
Running
NV Media Card
Optimization
Operation
Table 5-6 KI-Keypad set-up parameters
Parameters
Keypad.00 Language
Keypad.01 Show Units
Keypad.02 Backlight Level
Keypad.03 Keypad Date
Keypad.04 Keypad Time
Show Raw Text Parameter
Keypad.05
Values
Keypad.06 Software Version
NOTE
It is not possible to access the keypad parameters via any
communications channel.
5.5.2

Display messages

The following tables indicate the various possible mnemonics which can
be displayed by the drive and their meaning.
Table 5-7 Status indications
Upper row
string
The drive is inhibited and cannot be run.
The Safe Torque Off signal is not applied to
Safe Torque Off terminals or Pr 06.015 is
Inhibit
set to 0. The other conditions that can
prevent the drive from enabling are shown
as bits in Enable Conditions (06.010)
The drive is ready to run. The drive enable
Ready
is active, but the drive inverter is not active
because the final drive run is not active
Stop
The drive is stopped / holding zero speed
Run
The drive is active and running
Supply Loss
Supply loss condition has been detected
The motor is being decelerated to zero
Deceleration
speed / frequency because the final drive
run has been deactivated
dc injection
The drive is applying dc injection braking
The drive has tripped and no longer
Trip
controlling the motor. The trip code
appears in the lower display
Under
The drive is in the under voltage state
Voltage
either in low voltage or high voltage mode
Heat
The motor pre-heat function is active
The drive is performing a 'phasing test on
Phasing
enable'
or
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
Range
Classic English (0)
English (1)
Off (0), On (1)
0 to 100 %
01.01.10 to
31.12.99
00:00:00 to
23:59:59
Off (0), On (1)
00.00.00.00 to
99.99.99.99
Description
UL listing
information
Type
RW
RW
RW
RO
RO
RW
RO
Drive
output
stage
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
107

Hide quick links: