Alarm indications

An alarm is an indication given on the display by alternating the alarm
string with the drive status string on the upper row and showing the
alarm symbol in the last character in the upper row. Alarms strings are
not displayed when a parameter is being edited, but the user will still see
the alarm character on the upper row.
Table 5-8 Alarm indications
Alarm string
Motor Protection Accumulator (04.019) in the drive
Motor Overload
has reached 75.0 % of the value at which the drive
will trip and the load on the drive is >100 %.
Drive over temperature. Percentage Of Drive
Drive Overload
Thermal Trip Level (07.036) in the drive is greater
than 90 %.
The autotune procedure has been initialized and an
Auto Tune
autotune in progress.
Table 5-9 Option module and NV media card and other status
indications at power-up
First row
Second row string
string
Booting
Parameters
Drive parameters are being loaded from a NV Media Card
Booting
User Program
User program is being loaded from a NV Media Card to the drive
Option
Booting
Program
User program is being loaded from a NV Media Card to the option
module in slot X
Writing To
NV Card
Data is being written to a NV Media Card to ensure that its copy of the
drive parameters is correct because the drive is in Auto or Boot mode
Waiting For
Power System
The drive is waiting for the processor in the power stage to respond
after power-up
Waiting For
Options
The drive is waiting for the options modules to respond after power-up
Uploading
Options
From
At power-up it may be necessary to update the parameter database
held by the drive because an option module has changed or because
an applications module has requested changes to the parameter
structure. This may involve data transfer between the drive an option
modules. During this period 'Uploading From Options' is displayed
108
Electrical
Getting
Basic
installation
started
parameters
the motor
Description
Status
Parameters are being loaded
User program being loaded
User program being loaded
Data being written to NV Media
Card
Waiting for power stage
Waiting for an option module
Loading parameter database
Running
NV Media Card
Optimization
Operation
5.6

Changing the operating mode

Changing the operating mode returns all parameters to their default
value, including the motor parameters. User security status (00.049) and
User security code (00.034) are not affected by this procedure).
Procedure
Use the following procedure only if a different operating mode is
required:
1. Ensure the drive is not enabled, i.e. terminal 29 is open or Pr 06.015
is OFF (0)
2. Enter either of the following values in Pr mm.000, as appropriate:
1253 (50 Hz AC supply frequency)
1254 (60 Hz AC supply frequency)
3. Change the setting of Pr 00.048 as follows:
Pr 00.048 setting
The figures in the second column apply when serial communications are
used.
4. Either:
Press the red
Toggle the reset digital input
Carry out a drive reset through serial communications by setting
Pr 10.038 to 100.
NOTE
Entering 1253 or 1254 in Pr mm.000 will only load defaults if the setting
of Pr 00.048 has been changed.
5.7

Saving parameters

When changing a parameter in Menu 0, the new value is saved when
pressing the
parameter edit mode.
If parameters have been changed in the advanced menus, then the
change will not be saved automatically. A save function must be carried
out.
Procedure
1. Select 'Save Parameters'* in Pr mm.000 (alternatively enter a value
of 1000* in Pr mm.000)
2. Either:
Press the red
Toggle the reset digital input, or
Carry out a drive reset through serial communications by setting
Pr 10.038 to 100
* If the drive is in the under voltage state (i.e. when the control terminal 1
& 2 are being supplied from a low voltage DC supply) a value of 1001
must be entered into Pr mm.000 to perform a save function.
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
data
Operating mode
1
2
3
reset button
Enter button to return to parameter view mode from
reset button
Powerdrive F300 User Guide