Connecting Using The Fisher Easy-Drive Configuration Software - Emerson Fisher easy-Drive 200R Instruction Manual

Table of Contents

Advertisement

easy-Drive 200R
November 2023
Connecting using the Fisher easy­Drive configuration software
The Fisher easy­Drive Configurator software allows configuration and diagnosing of the Fisher easy­Drive electric
actuator with a graphical interface. Connect a PC to the actuator using a serial or USB to RS-485 device using the wiring
instructions above. The USB or serial device will be visible in the drop menu under Serial Port in the Manual Computer
Connection settings. Address baud rate, parity, stop bits, and byte order should be set to the Modbus settings of the
actuator. See Modbus Setup above for default actuator settings. Press the AUTO button in the upper left corner to
attempt to scan for and enable from the Preferences in the upper right.
Use the Fisher easy­Drive configuration software (figure 10) to make the desired changes, or register values may be
changed to allow different functionality.
Valve Type Configuration
D Valve Type
H Rotary: CW (clockwise to close)
H Rotary: CCW (counterclockwise to close)
Figure 11. Fisher easy-Drive Configuration Software
The easy-Drive 200R limits travel using hard stops that define the full range (max 104° rotation). Adjustable Travel
Stops are provided to allow for adjustments to travel to meet the application requirements, and for valve
alignment/calibration. See Actuator Mounting Section for more information on configuring the adjustable travel
stops.