Changing Over Units For The Technology Controller; Changing Of The Units With Starter - Siemens SINAMICS G120 Operating Instructions Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Functions
8.9 Application-specific functions
8.9.1.4

Changing over units for the technology controller

Note
We recommend that the units and reference values of the technology controller are
coordinated and harmonized with one another during commissioning.
Subsequent modification in the reference variable or the unit can result in incorrect
calculations or displays.
Changing over process variables of the technology controller
You change over the process variables of the technology controller using p0595. For
physical values, you define the reference variable in p0596.
The parameters affected by changing over units of the technology controller belong to unit
group 9_1. For details, please refer to the section titled "Unit group and unit choice" in the
List Manual.
8.9.1.5

Changing of the units with STARTER

The converter must be in the offline mode in order to change over the units.
STARTER shows whether you change settings online in the converter or change offline in
the PC (
You switch over the mode using the adjacent
buttons in the menu bar.
200
/
).
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB