Settings; Monitored Data; Operation Principle - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 13
Monitoring
13.5.5
Table 311:
CNTGGIO Group settings (basic)
Name
Operation
13.5.6
13.5.7
382
Name
COUNTER5
COUNTER6
RESET
Table 310:
CNTGGIO Output signals
Name
VALUE1
VALUE2
VALUE3
VALUE4
VALUE5
VALUE6

Settings

Values (Range)
Unit
Off
-
On

Monitored data

Table 312:
CNTGGIO Monitored data
Name
VALUE1
VALUE2
VALUE3
VALUE4
VALUE5
VALUE6

Operation principle

Event counter (CNTGGIO) has six counter inputs. CNTGGIO stores how many
times each of the inputs has been activated. The counter memory for each of the six
inputs is updated, giving the total number of times the input has been activated, as
soon as an input is activated. The maximum count up speed is 10 pulses per
second. The maximum counter value is 10 000. For counts above 10 000 the
counter will stop at 10 000 and no restart will take place.
Type
Default
Description
BOOLEAN
0
Input for counter 5
BOOLEAN
0
Input for counter 6
BOOLEAN
0
Reset of function
Type
Description
INTEGER
Output of counter 1
INTEGER
Output of counter 2
INTEGER
Output of counter 3
INTEGER
Output of counter 4
INTEGER
Output of counter 5
INTEGER
Output of counter 6
Step
Default
-
Off
Type
Values (Range)
INTEGER
-
INTEGER
-
INTEGER
-
INTEGER
-
INTEGER
-
INTEGER
-
1MRK 502 034-UEN -
Description
Operation Off / On
Unit
Description
-
Output of counter 1
-
Output of counter 2
-
Output of counter 3
-
Output of counter 4
-
Output of counter 5
-
Output of counter 6