Function Block; Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
8.5.3
8.5.4
Technical Manual
x E3
x E3
N
N N
RN
RN
uN
uN
x
Samples of the
neutral voltage
from which the
fundamental and
3rd harmonic
Neutral point fundamental frequency
voltages are
filtered out
over- voltage protection 10% – 100%
3rd harmonic
Differential
differential
0% – 30%
0% - 30%
IEC10000202 V1 EN
Figure 125:
Protection principles for STEFPHIZ function

Function block

STEFPHIZ
NEUTVOLT*
TRIP
TERMVOLT*
TRIP3H
CBCLOSED
TRIPUN
BLOCK
START
BLOCK3RD
START3H
BLOCKUN
STARTUN
DU3
BU3
IEC07000033-3-en.vsd
IEC07000033 V3 EN
Figure 126:
STEFPHIZ function block

Signals

Table 150:
STEFPHIZ Input signals
Name
Type
NEUTVOLT
GROUP
SIGNAL
TERMVOLT
GROUP
SIGNAL
CBCLOSED
BOOLEAN
BLOCK
BOOLEAN
BLOCK3RD
BOOLEAN
BLOCKUN
BOOLEAN
stator winding
stator winding
(1- x) E3
(1- x) E3
Rf
Rf
1 - x
1 - x
1 or 100 %
over-voltage protection 5% - 100%
Default
Description
-
Voltage connection neutral side
-
Open-Delta connection on Terminal side
1
Input 1 (TRUE) means breaker between gen. & tr.
is closed
0
Complete block of the stator earth fault protecion
function
0
Block of the 3rd harmonic-based parts of the
protection
0
Block of the fund. harmonic-based part of the
protection
Section 8
Voltage protection
CB 1 may not exist
CB 1 may not exist
CB 1
CB 1
T
T
Transformer
uT
uT
Samples of the
terminal voltage
from which the
3rd harmonic
voltage is filtered
out
IEC10000202-1-en.vsd
CB 2
CB 2