Signals; Settings; Operation Principle - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
10.2.4
10.2.5
Table 178:
TCSSCBR Non group settings (basic)
Name
Values (Range)
Operation
tDelay
10.2.6
Technical Manual

Signals

Table 176:
TCSSCBR Input signals
Name
TCS_STATE
BLOCK
Table 177:
TCSSCBR Output signals
Name
ALARM

Settings

Unit
Off
-
On
0.020 - 300.000
s

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of trip circuit supervision can be described by using a module
diagram. All the modules in the diagram are explained in the next sections.
GUID-9D3B79CB-7E06-4260-B55F-B7FA004CB2AC V1 EN
Figure 143:
Functional module diagram
Trip circuit supervision generates a current of approximately 1.0
mA through the supervised circuit. It must be ensured that this
current will not cause a latch up of the controlled object.
Secondary system supervision
Type
Default
Description
BOOLEAN
0
Trip circuit fail indication from I/O-card
BOOLEAN
0
Block of function
Type
Description
BOOLEAN
Trip circuit fault indication
Step
Default
-
On
0.001
3.000
Section 10
Description
Operation Off/On
Operate time delay
279