Function Block; Signals; Settings; Ied Commands With Position And Select For Iec 60870-5-103 - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 11
Control
11.11.2
11.11.3
11.11.4
Table 221:
I103GENCMD Non group settings (basic)
Name
FunctionType
PulseLength
InfNo
11.12
11.12.1
314

Function block

I103GENCMD
BLOCK
^CMD_OFF
^CMD_ON
IEC10000285-1-en.vsd
IEC10000285 V1 EN
Figure 159:
I103GENCMD function block

Signals

Table 219:
I103GENCMD Input signals
Name
BLOCK
Table 220:
I103GENCMD Output signals
Name
CMD_OFF
CMD_ON

Settings

Values (Range)
Unit
1 - 127
-
0.000 - 60.000
s
32 - 239
-
IED commands with position and select for IEC
60870-5-103 I103POSCMD

Functionality

I103POSCMD has double-point position indicators that are getting the position
value as an integer (for example from the POSITION output of the SCSWI
function block) and sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE); as
per standard, 0 and 3 values of the position are not supported.
The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used
Type
Default
Description
BOOLEAN
0
Block of command
Type
Description
BOOLEAN
Command output OFF
BOOLEAN
Command output ON
Step
Default
1
1
0.001
0.400
1
32
1MRK 502 034-UEN -
Description
Function type (1-255)
Pulse length
Information number for command output
(1-255)
Technical Manual