Technical Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 7
Current protection
7.10.8
216
This undervoltage with additional ACT logic can be used to provide funcionality
for overcurrent protection with undervoltage seal-in.

Technical data

Table 125:
VR2PVOC technical data
Function
Range or value
Start overcurrent
(2 - 5000)% of IBase
Definite time delay
(0.00 - 6000.00) s
Inverse
17 curves type
characteristics, see
table 481, table
482
and table
483
Operate time start
30 ms typically at 0 to 2 x I
overcurrent
20 ms typically at 0 to 10 x I
Reset time start
40 ms typically at 2 to 0 x I
overcurrent
Start undervoltage
(2.0 - 100.0)% of UBase
Operate time start
30 ms typically 2 to 0 x U
undervoltage
Reset time start
40 ms typically at 0 to 2 x U
undervoltage
High voltage limit,
(30 - 100)% of UBase
voltage dependent
operation
Reset ratio,
> 95%
overcurrent
Reset ratio,
< 105%
undervoltage
Overcurrent:
Critical impulse time
10 ms typically at 0 to 2 x I
Impulse margin time
15 ms typically
Accuracy
± 1.0% of I
± 1.0% of I at I>I
± 0.5% ± 25 ms
See table 481, table
table483
-
set
set
-
set
± 0.5 % of U
-
set
-
set
± 1.0 % of U
-
-
-
set
1MRK 502 034-UEN -
at I<I
r
r
r
482
and
r
r
Technical Manual