Function Block; Signals; Settings; Operation Principle - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
16.6.3
16.6.4
16.6.5
16.6.6
Technical Manual
signal to a logical zero, CHNGLCK is deactivated. If any logic is included in the
signal path to the CHNGLCK input, that logic must be designed so that it cannot
permanently issue a logical one on the CHNGLCK input. If such a situation would
occur in spite of these precautions, then please contact the local ABB
representative for remedial action.

Function block

CHNGLCK
LOCK*
ACTIVE
OVERRIDE
IEC09000062-1-en.vsd
IEC09000062 V1 EN
Figure 244:
CHNGLCK function block

Signals

Table 418:
CHNGLCK Input signals
Name
Type
LOCK
BOOLEAN
Table 419:
CHNGLCK Output signals
Name
Type
ACTIVE
BOOLEAN
OVERRIDE
BOOLEAN

Settings

The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600)

Operation principle

The Change lock function (CHNGLCK) is configured using ACT.
The function, when activated, will still allow the following changes of the IED
state that does not involve reconfiguring of the IED:
Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Basic IED functions
Default
Description
0
Activate change lock
Description
Change lock active
Change lock override
Section 16
501