Signals; Settings; Operation Principle - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
11.4.4
11.4.5
Table 201:
VSGGIO Non group settings (basic)
Name
Values (Range)
Operation
CtlModel
Mode
tSelect
tPulse
11.4.6
Technical Manual

Signals

Table 199:
VSGGIO Input signals
Name
BLOCK
PSTO
IPOS1
IPOS2
Table 200:
VSGGIO Output signals
Name
BLOCKED
POSITION
POS1
POS2
CMDPOS12
CMDPOS21

Settings

Unit
Off
-
On
Dir Norm
-
SBO Enh
Steady
-
Pulsed
0.000 - 60.000
s
0.000 - 60.000
s

Operation principle

Selector mini switch (VSGGIO) function can be used for double purpose, in the
same way as switch controller (SCSWI) functions are used:
for indication on the single line diagram (SLD). Position is received through
the IPOS1 and IPOS2 inputs and distributed in the configuration through the
POS1 and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
for commands that are received via the local HMI or IEC 61850 and
distributed in the configuration through outputs CMDPOS12 and CMDPOS21.
Type
Default
Description
BOOLEAN
0
Block of function
INTEGER
0
Operator place selection
BOOLEAN
0
Position 1 indicating input
BOOLEAN
0
Position 2 indicating input
Type
Description
BOOLEAN
The function is active but the functionality is
blocked
INTEGER
Position indication, integer
BOOLEAN
Position 1 indication, logical signal
BOOLEAN
Position 2 indication, logical signal
BOOLEAN
Execute command from position 1 to position 2
BOOLEAN
Execute command from position 2 to position 1
Step
Default
-
Off
-
Dir Norm
-
Pulsed
0.001
30.000
0.001
0.200
Section 11
Description
Operation Off / On
Specifies the type for control model
according to IEC 61850
Operation mode
Max time between select and execute
signals
Command pulse lenght
Control
303