Section 7
Current protection
7.6.8
7.7
7.7.1
7.7.2
7.7.2.1
192
Technical data
Table 93:
CCRPLD technical data
Function
Operate value, current
asymmetry level
Reset ratio
Time delay
Directional over-/under-power protection
GOPPDOP/GUPPDUP
Functionality
The directional over-/under-power protection GOPPDOP/GUPPDUP can be used
wherever a high/low active, reactive or apparent power protection or alarming is
required. The functions can alternatively be used to check the direction of active or
reactive power flow in the power system. There are a number of applications where
such functionality is needed. Some of them are:
•
detection of reversed active power flow
•
detection of high reactive power flow
Each function has two steps with definite time delay. Reset times for both steps can
be set as well.
Directional overpower protection GOPPDOP
Identification
Function description
Directional overpower protection
Range or value
(0-100) %
>95%
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
GOPPDOP
DOCUMENT172362-IMG158942
1MRK 502 034-UEN -
Accuracy
± 1.0% of I
r
-
± 0.5% ± 25 ms
ANSI/IEEE C37.2
device number
32
P >
V1 EN
Technical Manual