Technical Data; Directional Over-/Under-Power Protection Goppdop/Guppdup; Functionality; Directional Overpower Protection Goppdop - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 7
Current protection
7.6.8
7.7
7.7.1
7.7.2
7.7.2.1
192

Technical data

Table 93:
CCRPLD technical data
Function
Operate value, current
asymmetry level
Reset ratio
Time delay
Directional over-/under-power protection
GOPPDOP/GUPPDUP

Functionality

The directional over-/under-power protection GOPPDOP/GUPPDUP can be used
wherever a high/low active, reactive or apparent power protection or alarming is
required. The functions can alternatively be used to check the direction of active or
reactive power flow in the power system. There are a number of applications where
such functionality is needed. Some of them are:
detection of reversed active power flow
detection of high reactive power flow
Each function has two steps with definite time delay. Reset times for both steps can
be set as well.

Directional overpower protection GOPPDOP

Identification

Function description
Directional overpower protection
Range or value
(0-100) %
>95%
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
GOPPDOP
DOCUMENT172362-IMG158942
1MRK 502 034-UEN -
Accuracy
± 1.0% of I
r
-
± 0.5% ± 25 ms
ANSI/IEEE C37.2
device number
32
P >
V1 EN
Technical Manual