Monitored Data; Operation Principle; Measurements; Functionality - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 13
Monitoring
Name
MV lLim
MV llLim
MV min
MV max
MV dbType
MV limHys
13.3.6
13.3.7
13.4
13.4.1
350
Values (Range)
Unit
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
Cyclic
-
Dead band
Int deadband
0.000 - 100.000
%

Monitored data

Table 277:
MVGGIO Monitored data
Name
VALUE
RANGE

Operation principle

Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range,
as output values. In the same time, it will send over IEC 61850-8-1 the value, to
other IEC 61850 clients in the substation.

Measurements

Functionality

Measurement functions is used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM600 or to station level for
example, via IEC 61850. The possibility to continuously monitor measured values
of active power, reactive power, currents, voltages, frequency, power factor etc. is
vital for efficient production, transmission and distribution of electrical energy. It
provides to the system operator fast and easy overview of the present status of the
power system. Additionally, it can be used during testing and commissioning of
protection and control IEDs in order to verify proper operation and connection of
Step
Default
0.01
-800.00
0.01
-900.00
0.01
-1000.00
0.01
1000.00
-
Dead band
0.001
5.000
Type
Values (Range)
REAL
-
INTEGER
0=Normal
1=High
2=Low
3=High-High
4=Low-Low
1MRK 502 034-UEN -
Description
Low limit multiplied with the base prefix
(multiplication factor)
Low Low limit multiplied with the base
prefix (multiplication factor)
Minimum value multiplied with the base
prefix (multiplication factor)
Maximum value multiplied with the base
prefix (multiplication factor)
Reporting type
Hysteresis value in % of range (common
for all limits)
Unit
Description
-
Magnitude of deadband
value
-
Range
Technical Manual

Advertisement