Section 16
Basic IED functions
16.2.4.2
486
Table 403:
Explanations of internal signals
Name of signal
Internal Fail
Internal Warning
Real Time Clock Error
Time Synch Error
Runtime Exec Error
IEC61850 Error
SW Watchdog Error
Runtime App Error
Settings Changed
Setting Groups Changed
Change Lock
File System Error
DNP3 Error

Run-time model

The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification, see
239.
Reasons for activation
This signal will be active if one or more of the following
internal signals are active; Real Time Clock Error, Runtime
App Error, Runtime Exec Error, SW Watchdog Error, File
System Error
This signal will be active if one or more of the following
internal signals are active; IEC 61850 Error, DNP3 Error
This signal will be active if there is a hardware error with
the real time clock.
This signal will be active when the source of the time
synchronization is lost, or when the time system has to
make a time reset.
This signal will be active if the Runtime Engine failed to do
some actions with the application threads. The actions can
be loading of settings or parameters for components,
changing of setting groups, loading or unloading of
application threads.
This signal will be active if the IEC 61850 stack did not
succeed in some actions like reading IEC 61850
configuration, startup, for example.
This signal will be activated when the IED has been under
too heavy load for at least 5 minutes. The operating
systems background task is used for the measurements.
This signal will be active if one or more of the application
threads are not in the state that Runtime Engine expects.
The states can be CREATED, INITIALIZED, RUNNING, for
example.
This signal will generate an internal event to the internal
event list if any settings are changed.
This signal will generate an internal event to the Internal
Event List if any setting groups are changed.
This signal will generate an internal Event to the Internal
Event List if the Change Lock status is changed
This signal will be active if both the working file and the
backup file are corrupted and cannot be recovered.
This signal will be active when DNP3 detects any
configuration error during startup.
1MRK 502 034-UEN -
Figure
Technical Manual