Settings; Operation Principle; Bay Control Qcbay - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 11
Control
11.2.4.5
11.2.5
11.2.5.1
296
Table 193:
LOCREMCTRL Output signals
Name
Type
HMICTR1
INTEGER
HMICTR2
INTEGER
HMICTR3
INTEGER
HMICTR4
INTEGER
HMICTR5
INTEGER
HMICTR6
INTEGER
HMICTR7
INTEGER
HMICTR8
INTEGER
HMICTR9
INTEGER
HMICTR10
INTEGER
HMICTR11
INTEGER
HMICTR12
INTEGER

Settings

The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).

Operation principle

Bay control QCBAY

The functionality of the Bay control (QCBAY) function is not defined in the IEC
61850–8–1 standard, which means that the function is a vendor specific logical node.
The function sends information about the Permitted Source To Operate (PSTO)
and blocking conditions to other functions within the bay for example, switch
control functions, voltage control functions and measurement functions.
Local panel switch
The local panel switch is a switch that defines the operator place selection. The
switch connected to this function can have three positions remote/local/off. The
positions are here defined so that remote means that operation is allowed from station/
remote level and local from the IED level. The local/remote switch is normally
situated on the control/protection IED itself, which means that the position of the
switch and its validity information are connected internally, and not via I/O boards.
When the switch is mounted separately on the IED the signals are connected to the
function via I/O boards.
When the local panel switch is in Off position all commands from remote and local
level will be ignored. If the position for the local/remote switch is not valid the
PSTO output will always be set to faulty state (3), which means no possibility to
operate.
Description
Bitmask output 1 to local remote LHMI input
Bitmask output 2 to local remote LHMI input
Bitmask output 3 to local remote LHMI input
Bitmask output 4 to local remote LHMI input
Bitmask output 5 to local remote LHMI input
Bitmask output 6 to local remote LHMI input
Bitmask output 7 to local remote LHMI input
Bitmask output 8 to local remote LHMI input
Bitmask output 9 to local remote LHMI input
Bitmask output 10 to local remote LHMI input
Bitmask output 11 to local remote LHMI input
Bitmask output 12 to local remote LHMI input
1MRK 502 034-UEN -
Technical Manual