1MRK 502 034-UEN -
8.2
8.2.1
8.2.2
Technical Manual
Function
Range or value
Definite time delay,
(0.00 - 6000.00) s
step 1
Definite time delays,
(0.000-60.000) s
step 2
Minimum operate
(0.000–60.000) s
time, inverse
characteristics
Operate time, start
30 ms typically at 2 to 0.5 x U
function
Reset time, start
40 ms typically at 0.5 to 2 x U
function
Critical impulse time
10 ms typically at 2 to 0 x U
Impulse margin time
15 ms typically
Two step overvoltage protection OV2PTOV
Identification
Function description
Two step overvoltage protection
Functionality
Overvoltages may occur in the power system during abnormal conditions such as
sudden power loss, tap changer regulating failures, open line ends on long lines etc.
OV2PTOV has two voltage steps, where step 1 can be set as inverse or definite
time delayed. Step 2 is always definite time delayed.
OV2PTOV has an extremely high reset ratio to allow settings close to system
service voltage.
Voltage protection
Accuracy
± 0.5% ± 25 ms
± 0.5% ±25 ms
± 0.5% ± 25 ms
-
set
-
set
-
set
-
IEC 61850
IEC 60617
identification
identification
OV2PTOV
2U>
SYMBOL-C-2U SMALLER THAN
V1 EN
Section 8
ANSI/IEEE C37.2
device number
59