Section 10
Secondary system supervision
10.1.8
10.2
10.2.1
10.2.2
10.2.3
278
Technical data
Table 175:
SDDRFUF technical data
Function
Operate voltage, zero sequence
Operate current, zero sequence
Operate voltage, negative sequence
Operate current, negative sequence
Operate voltage change level
Operate current change level
Operate phase voltage
Operate phase current
Operate phase dead line voltage
Operate phase dead line current
Breaker close/trip circuit monitoring TCSSCBR
Identification
Function description
Breaker close/trip circuit monitoring
Functionality
The trip circuit supervision function TCSSCBR is designed to supervise the control
circuit of the circuit breaker. The invalidity of a control circuit is detected by using
a dedicated output contact that contains the supervision functionality.
The function operates after a predefined operating time and resets when the fault
disappears.
Function block
GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
Figure 142:
Function block
Range or value
(1-100)% of UBase
(1–100)% of IBase
(1–100)% of UBase
(1–100)% of IBase
(1–100)% of UBase
(1–100)% of IBase
(1-100)% of UBase
(1-100)% of IBase
(1-100)% of UBase
(1-100)% of IBase
IEC 61850
IEC 60617
identification
identification
TCSSCBR
-
1MRK 502 034-UEN -
Accuracy
± 1.0% of U
r
± 1.0% of I
r
± 0.5% of U
r
± 1.0% of I
r
± 5.0% of U
r
± 5.0% of I
r
± 0.5% of U
r
± 1.0% of I
r
± 0.5% of U
r
± 1.0% of I
r
ANSI/IEEE C37.2
device number
-
Technical Manual