Section 13
Monitoring
13.4.2
13.4.2.1
13.4.2.2
352
The power system quantities provided, depends on the actual
hardware, (TRM) and the logic configuration made in PCM600.
The measuring functions CMSQI and VMSQI provide sequential quantities:
I: sequence currents (positive, zero, negative sequence, amplitude and angle)
U: sequence voltages (positive, zero and negative sequence, amplitude and
angle).
The CVMMXN function calculates three-phase power quantities by using
fundamental frequency phasors (DFT values) of the measured current respectively
voltage signals. The measured power quantities are available either, as
instantaneously calculated quantities or, averaged values over a period of time (low
pass filtered) depending on the selected settings.

Measurements CVMMXN

Identification

Function description
Measurements

Function block

The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
CVMMXN
I3P*
S
U3P*
S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE
IEC08000222.vsd
IEC08000222 V1 EN
Figure 183:
CVMMXN function block
IEC 61850
IEC 60617
identification
identification
CVMMXN
P, Q, S, I, U, f
SYMBOL-RR V1 EN
1MRK 502 034-UEN -
ANSI/IEEE C37.2
device number
-