Section 16
Basic IED functions
16.5
16.5.1
16.5.2
16.5.3
16.5.4
498
The above example also includes five output signals, for confirmation of which
group that is active.

Test mode functionality TESTMODE

Identification

Function description
Test mode functionality

Functionality

When the Test mode functionality TESTMODE function is activated, protection
functions in the IED are automatically blocked. It is then possible to unblock the
protection functions individually from the local HMI or the Parameter Setting tool
to perform required tests.
When leaving TESTMODE, all blockings are removed and the IED resumes
normal operation. However, if during TESTMODE operation, power is removed
and later restored, the IED will remain in TESTMODE with the same protection
functions blocked or unblocked as before the power was removed. All testing will
be done with actually set and configured values within the IED. No settings will be
changed, thus mistakes are avoided.
Forcing of binary output signals is only possible when the IED is in test mode.

Function block

TESTMODE
INPUT
ACTIVE
OUTPUT
SETTING
NOEVENT
IEC09000219-1.vsd
IEC09000219 V1 EN
Figure 243:
TESTMODE function block

Signals

Table 415:
TESTMODE Input signals
Name
Type
INPUT
BOOLEAN
IEC 61850
IEC 60617
identification
identification
TESTMODE
Default
Description
0
Sets terminal in test mode when active
1MRK 502 034-UEN -
ANSI/IEEE C37.2
device number
-
-
Technical Manual