Section 12
Logic
12.8.5
12.8.6
344

Settings

The function does not have any parameters available in local HMI or Protection
and Control IED Manager (PCM600)

Operation principle

Integer to boolean conversion with logic node representation function (IB16FCVB)
is used to transform an integer into a set of 16 binary (logical) signals. IB16FCVB
function can receive an integer from a station computer – for example, over IEC
61850. The BLOCK input will freeze the logical outputs at the last value.
The operator position input (PSTO) determines the operator place. The integer
number can be written to the block while in "Remote". If PSTO is in "Off"
or "Local", then no change is applied to the outputs.
1MRK 502 034-UEN -
Technical Manual