Technical Data; Measured Value Expander Block Mvexp; Identification; Functionality - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
13.11.6
13.12
13.12.1
13.12.2
13.12.3
Technical Manual

Technical data

Table 332:
DRPRDRE technical data
Function
Buffer capacity
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of disturbance reports
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)

Measured value expander block MVEXP

Identification

Function description
Measured value expander block

Functionality

The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI
and VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low limit, high limit and high-
high limit. The measure value expander block has been introduced to enable
translating the integer output signal from the measuring functions to 5 binary
signals: below low-low limit, below low limit, normal, above high-high limit or
above high limit. The output signals can be used as conditions in the configurable
logic or for alarming purpose.

Function block

MVEXP
RANGE*
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC09000215-1-en.vsd
IEC09000215 V1 EN
Figure 203:
MVEXP function block
IEC 61850
IEC 60617
identification
identification
MVEXP
-
Section 13
Monitoring
Value
40
96
100
340 seconds (100
recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz
ANSI/IEEE C37.2
device number
-
421