Setting Parameters - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 3
Analog inputs
3.3
Table 1:
AISVBAS Non group settings (basic)
Name
PhaseAngleRef
40
Definition of direction
for directional functions
Reverse
Forward
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"
IEC05000456 V1 EN
Figure 2:
Internal convention of the directionality in the IED
The correct setting of the primary CT direction
CTStarPoint is set to FromObject or ToObject.
Positive quantities flow towards the object.
Direction is defined as Forward and looks towards the object.
The ratios of the main CTs and VTs must be known to use primary system
quantities for settings and calculation in the IED, The user has to set the rated
secondary and primary currents and voltages of the CTs and VTs to provide the
IED with this information.
The CT and VT ratio and the name on respective channel is done under Main
menu/Hardware/Analog modules in the Parameter Settings tool.

Setting parameters

Dependent on ordered IED type.
Values (Range)
Unit
TRM - Channel 1
-
TRM - Channel 2
TRM - Channel 3
TRM - Channel 4
TRM - Channel 5
TRM - Channel 6
TRM - Channel 7
TRM - Channel 8
TRM - Channel 9
TRM - Channel 10
Protected Object
Line, transformer, etc
Step
Default
-
TRM - Channel 1
1MRK 502 034-UEN -
Definition of direction
for directional functions
Forward
Reverse
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456.vsd
Description
Reference channel for phase angle
presentation
Technical Manual