Supplementary Criteria - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 5
Differential protection
5.3.6.3
108

Supplementary criteria

To relieve the burden of constructing an exact optimal operate-restrain
characteristic, two special features supplement the basic stabilized differential
protection function, making Generator differential protection GENPDIF a very
reliable one.
The supplementary criteria are:
Internal/external fault discriminator (enhances, or blocks, the trip command)
Harmonic restrain (blocks only)
The internal/external fault discriminator is a very reliable supplementary criterion.
It discriminates with a high speed between internal and external faults. The
discriminator is the main part of what is here called the negative-sequence-current-
based differential protections. It is recommended that this feature is always used
(that is, enabled, OpNegSeqDiff = On).
If a fault is classified as internal, then any eventual block signals by the harmonic
criterion are ignored, and the differential protection can operate very quickly
without any further delay.
If a fault (disturbance) is classified as external, then generally, but not
unconditionally, a trip command is prevented. If a fault is classified as external,
harmonic analysis of the fault conditions is initiated.
If all the differential currents which caused their respective start signals to be set,
are free of harmonic pollution, that is, if no harmonic block signal has been set,
then a (minor) internal fault, simultaneous with a predominant external fault, can
be suspected. This conclusion can be drawn because at external faults, major false
differential currents can only exist when one or more current transformers saturate
transiently. In this case, the false instantaneous differential currents are highly
polluted by higher harmonic components, the 2
The existence of relatively high negative-sequence currents is in itself an indication
of a disturbance, as the negative-sequence currents are superimposed, pure-fault
quantities. The negative-sequence currents are measurable indications of abnormal
conditions. The negative sequence currents are particularly suitable for directional
tests. The negative sequence internal or external fault discriminator works
satisfactorily even in case of three-phase faults. Because of the fundamental
frequency components (50/60 Hz) of the decaying DC offset of the fault currents,
the system is not fully symmetrical immediately after the fault. Due to the transient
existence of the negative sequence system, faults can be distinguished as internal or
external, even for three-phase faults.
The internal or external fault discriminator responds to the relative phase angles of
the negative sequence fault currents at both ends of the stator winding. Observe
that the source of the negative sequence currents at unsymmetrical faults is at the
fault point.
1MRK 502 034-UEN -
nd
th
, and the 5
.
Technical Manual