Outputs; Outputs For Tripping, Controlling And Signalling - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
17.3
17.3.1
Technical Manual
Terminal
Description
X339-8
Common - for inputs 4-5
X339-9
Binary input 4 +
X339-10
Binary input 5 +
X339-11
-
X339-12
Common - for inputs 6-7
X339-13
Binary input 6 +
X339-14
Binary input 7 +
X339-15
-
X339-16
Common - for inputs 8-9
X339-17
Binary input 8 +
X339-18
Binary input 9 +

Outputs

Outputs for tripping, controlling and signalling

Output contacts PO1, PO2 and PO3 are power output contacts used, for example,
for controlling circuit breakers.
Each signal connector terminal is connected with one 0.5...2.5 mm
2
two 0.5...1.0 mm
wires.
The connected DC voltage to outputs with trip circuit supervision
(TCS) must have correct polarity or the trip circuit supervision
TCSSCBR function will not operate properly.
Table 449:
Output contacts X307, 6U half 19"
Terminal
Description
Power output 1, normally open
(TCS)
X307-1
-
X307-2
+
Power output 2, normally open
(TCS)
X307-3
-
X307-4
+
Power output 3, normally open
(TCS)
Table continues on next page
Section 17
IED physical connections
PCM600 info
Hardware module
Hardware channel
instance
BIO_6
BI4
BIO_6
BI5
BIO_6
BI6
BIO_6
BI7
BIO_6
BI8
BIO_6
BI9
2
wire or with
PCM600 info
Hardware module
Hardware channel
instance
PSM_102
BO1_PO_TCS
PSM_102
BO2_PO_TCS
525

Advertisement

Table of Contents
loading