Circuit Breaker Operation Monitoring - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
13.15.7.2
Technical Manual
GUID-60ADC120-4B5A-40D8-B1C5-475E4634214B V1 EN
Figure 208:
Functional module diagram for monitoring circuit breaker status
Phase current check
This module compares the three phase currents with the setting AccDisLevel. If the
current in a phase exceeds the set level, information about phase is reported to the
contact position indicator module.
Contact position indicator
The circuit breaker status is open if the auxiliary input contact POSCLOSE is low,
the POSOPEN input is high and the current is zero. The circuit breaker is closed
when the POSOPEN input is low and the POSCLOSE input is high. The breaker is
in the intermediate position if both the auxiliary contacts have the same value, that
is, both are in the logical level "0", or if the auxiliary input contact POSCLOSE is
low and the POSOPEN input is high, but the current is not zero.
The status of the breaker is indicated with the binary outputs CBOPEN, CBINVPOS
and CBCLOSED for open, intermediate and closed position respectively.

Circuit breaker operation monitoring

The purpose of the circuit breaker operation monitoring subfunction is to indicate if
the circuit breaker has not been operated for a long time.
The operation of the circuit breaker operation monitoring can be described by using
a module diagram. All the modules in the diagram are explained in the next sections.
GUID-82C88B52-1812-477F-8B1A-3011A300547A V1 EN
Figure 209:
Functional module diagram for calculating inactive days and alarm
for circuit breaker operation monitoring
Section 13
Monitoring
433