15.2.3
Table 377:
IEC61850-8-1 Non group settings (basic)
Name
Operation
GOOSE
15.2.4
464
The event system has a rate limiter to reduce CPU load. The event channel has a
quota of 10 events/second. If the quota is exceeded the event channel transmission
is blocked until the event changes is below the quota, no event is lost.
All communication connectors, except for the front port connector, are placed on
integrated communication modules. The IED is connected to Ethernet-based
communication systems via the fibre-optic multimode LC connector (100BASE-FX).
The IED supports SNTP and IRIG-B time synchronization methods with a time-
stamping resolution of 1 ms.
Ethernet based: SNTP and DNP3
With time synchronization wiring: IRIG-B
The IED supports IEC 60870-5-103 time synchronization methods with a time
stamping resolution of 5 ms.
Table 376:
Supported communication interface and protocol alternatives
Interfaces/Protocols
IEC 61850-8-1
DNP3
IEC 60870-5-103
● = Supported

Settings

Values (Range)
Unit
Off
-
On
Front
-
LAN1

Technical data

Table 378:
IEC 61850-8-1 communication protocol
Function
Protocol
Communication speed for the IEDs
Ethernet
100BASE-FX LC
Step
Default
-
Off
-
LAN1
Value
IEC 61850-8-1
100BASE-FX
1MRK 502 034-UEN -
ST connector
Description
Operation Off/On
Port for GOOSE communication
Technical Manual