Section 13
Monitoring
13.21.2
13.21.3
13.21.4
Table 360:
I103IED Non group settings (basic)
Name
FunctionType
13.22
13.22.1
450
Function block
I103IED
BLOCK
19_LEDRS
21_TESTM
23_GRP1
24_GRP2
25_GRP3
26_GRP4
IEC10000292-1-en.vsd
IEC10000292 V1 EN
Figure 223:
I103IED function block
Signals
Table 359:
I103IED Input signals
Name
BLOCK
19_LEDRS
21_TESTM
23_GRP1
24_GRP2
25_GRP3
26_GRP4
Settings
Values (Range)
Unit
1 - 255
-
Supervison status for IEC 60870-5-103
I103SUPERV
Functionality
I103SUPERV is a function block with defined functions for supervision indications
in monitor direction. This block includes the FunctionType parameter, and the
information number parameter is defined for each output signal.
Type
Default
Description
BOOLEAN
0
Block of status reporting
BOOLEAN
0
Information number 19, reset LEDs
BOOLEAN
0
Information number 21, test mode is active
BOOLEAN
0
Information number 23, setting group 1 is active
BOOLEAN
0
Information number 24, setting group 2 is active
BOOLEAN
0
Information number 25, setting group 3 is active
BOOLEAN
0
Information number 26, setting group 4 is active
Step
Default
1
1
1MRK 502 034-UEN -
Description
Function type (1-255)
Technical Manual