Section 13
Monitoring
13.12.4
13.12.5
13.12.6
422

Signals

Table 333:
MVEXP Input signals
Name
Type
RANGE
INTEGER
Table 334:
MVEXP Output signals
Name
Type
HIGHHIGH
BOOLEAN
HIGH
BOOLEAN
NORMAL
BOOLEAN
LOW
BOOLEAN
LOWLOW
BOOLEAN

Settings

The function does not have any parameters available in Local HMI or Protection
and Control IED Manager (PCM600).
Common base IED values for primary current (IBase), primary voltage (UBase)
and primary power (SBase) are set in a Global base values for settings function
GBASVAL. Setting GlobalBaseSel is used to select a GBASVAL function for
reference of base values.

Operation principle

The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO).
The function block converts the input integer value to five binary output signals
according to
table
335.
Table 335:
Input integer value converted to binary output signals
Measured supervised
below low-low
value is:
limit
Output:
LOWLOW
High
LOW
NORMAL
HIGH
HIGHHIGH
Default
Description
0
Measured value range
Description
Measured value is above high-high limit
Measured value is between high and high-high limit
Measured value is between high and low limit
Measured value is between low and low-low limit
Measured value is below low-low limit
between low‐
between low
low and low
and high limit
limit
High
High
1MRK 502 034-UEN -
between high-
above high-
high and high
high limit
limit
High
High
Technical Manual