ABB REG650 Technical Manual page 567

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
Technical Manual
A1
I>
t=0
t=t
1
IEC05000132 V1 EN
Figure 255:
Selectivity steps for a fault on feeder B1
where:
t=0
is The fault occurs
t=t
is Protection B1 trips
1
t=t
is Breaker at B1 opens
2
t=t
is Protection A1 resets
3
In the case protection B1 shall operate without any intentional delay
(instantaneous). When the fault occurs the protections start to detect the fault
current. After the time t
The protection A1 starts its delay timer at the same time, with some deviation in
time due to differences between the two protections. There is a possibility that A1
will start before the trip is sent to the B1 circuit breaker.
At the time t
the circuit breaker B1 has opened its primary contacts and thus the
2
fault current is interrupted. The breaker time (t2 - t1) can differ between different
faults. The maximum opening time can be given from manuals and test protocols.
Still at t
the timer of protection A1 is active.
2
At time t
the protection A1 is reset, i.e. the timer is stopped.
3
In most applications it is required that the delay times shall reset as fast as possible
when the current fed to the protection drops below the set current level, the reset
time shall be minimized. In some applications it is however beneficial to have
some type of delayed reset time of the overcurrent function. This can be the case in
the following applications:
Time inverse characteristics
B1
I>
t=t
t=t
2
3
the protection B1 send a trip signal to the circuit breaker.
1
Section 20
Feeder
Time axis
en05000132.vsd
561