Settings; Operation Principle - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 034-UEN -
11.6.5
Table 206:
SPC8GGIO Non group settings (basic)
Name
Values (Range)
Operation
Latched1
tPulse1
Latched2
tPulse2
Latched3
tPulse3
Latched4
tPulse4
Latched5
tPulse5
Latched6
tPulse6
Latched7
tPulse7
Latched8
tPulse8
11.6.6
Technical Manual

Settings

Unit
Off
-
On
Pulsed
-
Latched
0.01 - 6000.00
s
Pulsed
-
Latched
0.01 - 6000.00
s
Pulsed
-
Latched
0.01 - 6000.00
s
Pulsed
-
Latched
0.01 - 6000.00
s
Pulsed
-
Latched
0.01 - 6000.00
s
Pulsed
-
Latched
0.01 - 6000.00
s
Pulsed
-
Latched
0.01 - 6000.00
s
Pulsed
-
Latched
0.01 - 6000.00
s

Operation principle

The PSTO input will determine which the allowed position for the operator
(LOCAL, REMOTE, ALL) is. Upon sending a command from an allowed operator
position, one of the 8 outputs will be activated. The settings Latchedx and tPulsex
(where x is the respective output) will determine if the signal will be pulsed (and
how long the pulse is) or latched (steady). BLOCK will block the operation of the
function – in case a command is sent, no output will be activated.
PSTO is the universal operator place selector for all control
functions. Even if PSTO can be configured to allow LOCAL or
ALL operator positions, the only functional position usable with the
SPC8GGIO function block is REMOTE.
Step
Default
-
Off
-
Pulsed
0.01
0.10
-
Pulsed
0.01
0.10
-
Pulsed
0.01
0.10
-
Pulsed
0.01
0.10
-
Pulsed
0.01
0.10
-
Pulsed
0.01
0.10
-
Pulsed
0.01
0.10
-
Pulsed
0.01
0.10
Section 11
Description
Operation Off/On
Setting for pulsed/latched mode for
output 1
Output1 Pulse Time
Setting for pulsed/latched mode for
output 2
Output2 Pulse Time
Setting for pulsed/latched mode for
output 3
Output3 Pulse Time
Setting for pulsed/latched mode for
output 4
Output4 Pulse Time
Setting for pulsed/latched mode for
output 5
Output5 Pulse Time
Setting for pulsed/latched mode for
output 6
Output6 Pulse Time
Setting for pulsed/latched mode for
output 7
Output7 Pulse Time
Setting for pulsed/latched mode for
output 8
Output8 pulse time
Control
307