Measurement principle

Depending on the set ConnType value, UV2PTUV measures phase-to-earth or phase-
to-phase voltages and compare against set values, U1< and U2<. The parameters
OpMode1 and OpMode2 influence the requirements to activate the START
outputs. Either 1 out of 3, 2 out of 3, or 3 out of 3 measured voltages have to be
lower than the corresponding set point to issue the corresponding START signal.
To avoid oscillations of the output START signal, a hysteresis has been included.

Time delay

The time delay for step 1 can be either definite time delay (DT) or inverse time
delay (IDMT). Step 2 is always definite time delay (DT). For the inverse time
delay two different modes are available; inverse curve A and inverse curve B.
The type A curve is described as:
k
=
t
< -
æ
ö
U
U
ç
÷
<
è
U
ø
EQUATION1431 V1 EN
The type B curve is described as:
×
k
480
=
t
< -
æ
U
U
×
-
32
0.5
ç
<
è
U
EQUATION1432 V1 EN
3
+
0.055
2.0
ö
÷
ø
1MRK 502 034-UEN -
(Equation 64)
(Equation 65)
(Equation 66)
(Equation 67)