Function Block; Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 7
Current protection
7.3.3
7.3.4
166

Function block

SDEPSDE
I3P*
TRIP
U3P*
TRDIRIN
BLOCK
TRNDIN
BLKUN
TRUN
START
STDIRIN
STNDIN
STUN
STFW
STRV
STDIR
UNREL
IEC08000036 V1 EN
Figure 86:
SDEPSDE function block

Signals

Table 69:
SDEPSDE Input signals
Name
Type
I3P
GROUP
SIGNAL
U3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKUN
BOOLEAN
Table 70:
SDEPSDE Output signals
Name
Type
TRIP
BOOLEAN
TRDIRIN
BOOLEAN
TRNDIN
BOOLEAN
TRUN
BOOLEAN
START
BOOLEAN
STDIRIN
BOOLEAN
STNDIN
BOOLEAN
STUN
BOOLEAN
STFW
BOOLEAN
STRV
BOOLEAN
STDIR
INTEGER
UNREL
BOOLEAN
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Blocks the non-directional voltage residual outputs
Description
General trip signal
Trip of the directional residual overcurrent
Trip of non-directional residual overcurrent
Trip of non-directional residual overvoltage
General start signal
Start of the directional residual overcurrent function
Start of non directional residual overcurrent
Start of non directional residual overvoltage
Start of directional function for fault in forward
direction
Start of directional function for fault in reverse
direction
Direction of fault
Residual voltage release of operation of
directional modes
1MRK 502 034-UEN -