Table of Contents

Advertisement

FTX-N/U, FVXS-N, FDMQ-R Series
9.

Wiring

With a multi indoor unit
• Live the sensor securing plate, remove the front electrical wiring box cover, and connect the branch wiring to the terminal
block.
1) As shown in the illustration, insert the wires including the ground wire into the conduit and secure them with lock nut
onto the conduit mounting plate.
2) Strip wire ends (3/4 inch (20mm)).
3) Match wire colours with terminal numbers on indoor and outdoor unit's terminal blocks and firmly secure the wires in
the corresponding terminals with the screws.
4) Connect the ground wires to the corresponding terminals.
5) Pull the wires lightly to make sure they are securely connected.
6) Make sure that the wires do not come in contact with the metal conduit for the heat exchanger.
7) In case of connecting to an adapter system, run the remote controller cable and attach the S21. (Refer to "10. When
connecting to an HA system" on page 15.)
Sensor securing plate
Front electrical
wiring box cover
WARNING
• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating,
electric shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
01_EN_3P379970-7B.indd 14
, install as described in the installation manual supplied with the multi outdoor unit.
Shape wires so
Terminal block
that the front
1
2
3
electrical wiring
Electrical
box cover will fit
wiring
securely.
box
Wire retainer
Use the specified
wire type.
Make sure that the wires
do not come in contact
with the metal conduit
for the heat exchanger.
106
Back
Lock nut
Conduit
mounting
plate
Conduit
Firmly fix the wires with
the terminal screws.
Use AWG16 if the connection wire
length is less than 33ft (10m), or
AWG14 if it is 33ft (10m) or more.
1
Indoor
2
3
unit
Firmly fix the wires with
the terminal screws.
EDUS091558E
Outdoor unit
1 2 3
L
L
1
2
14
C: 3P379970-7B
11/12/2015 13:29:59