Daikin FTX-N/U Manual page 145

Table of Contents

Advertisement

FTX-N/U, FVXS-N, FDMQ-R Series
7-4
Press On/Off button within 10 sec-
onds, and the test operation starts.
Monitor the operation of the indoor unit
for a minimum of 10 minutes. During
test operation, the indoor unit will
continue to cool regardless of the
temperature setpoint and room
temperature.
Note) In the case of above-men-
7-5
Press
Menu/OK button in the basic
screen. Main menu is displayed.
7-6
In the case of a model having air ow
direction function, select
Air ow Direction
and check that air ow direction is
actuated according to the setting.
For operation of air ow direction
setting, see the operation manual.
7-7
After the operation of air ow direction
is con rmed, press Menu/OK button.
Basic screen returns.
7-8
Press and hold
4 seconds or longer in the basic
screen.
Service settings menu is displayed.
7-9
Select
settings menu, and press Menu/OK
button. Basic screen returns and
normal operation is conducted.
Note) The test operation will automat-
7-10
Check the functions according to the
operation manual.
7-11
When the decorative panel is not
installed, shut off the power supply
after the test operation  nishes.
If construction activities are planned within
the space following the test operation
procedure, recommend to the customer
that the indoor unit is not operated to
prevent contamination from paints, drywall
dust and other airborne materials.
16
01_EN_3P243521-7L.indd 16
7-3
tioned procedures
and
7-4
in reverse order, test
operation can start as well.
in the main menu
Cancel button for
Test Operation
in the service
ically  nish in 30 minutes.
7-
4
7-
5
Cool
Set temperature
28
°C
Test Operation
<Main menu screen>
7-
6
Main Menu
1/3
Airflow Direction
Individual Airflow Direction
Ventilation
Schedule
Off Timer
Celsius / Fahrenheit
Setting
7-
7
Airflow Direction
Swing
Setting
7-
8
Cool
Set temperature
28
°C
Test Operation
7-
9
Service Settings
1/3
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Setting
<Basic screen>
143
EDUS091558E
Press On/Off button
(within 10 seconds).
Press Menu/OK button.
Press Menu/OK button.
Change the air ow
direction by using
(Up/Down) button.
Press Menu/OK button.
Press and hold Cancel
button for 4 seconds or
longer while the backlight
is on.
Press Menu/OK button.
3P243521-7L
11/27/2014 11:21:45 AM

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fvxs-nFdmq-r series