Daikin FTX-N/U Manual page 144

Table of Contents

Advertisement

FTX-N/U, FVXS-N, FDMQ-R Series
Notes)
1.
Field settings are normally applied to the entire remote control group, however if individual
indoor units in the remote control group require speci c settings or for con rmation that
settings have been established, utilize the mode number in parenthesis.
2.
Any features not supported by the connected indoor unit will not be displayed.
3.
When mode 10-2-01 is selected, only the return air temperature value is reported to the
multizone controller.
4.
The actual default deadband value will depend upon the indoor unit model.
7.
Test Operation
Also see installation manuals furnished with the indoor unit and the
outdoor unit.
Verify that the wiring of the indoor unit and the outdoor unit is completed.
Ensure that covers have been replaced on electrical component boxes for both indoor and outdoor
units prior to restoring power.
After refrigerant piping, drain piping and electric wiring are completed, clean inside of the indoor unit
and decorative panel.
Perform the test operation according to following procedure.
To protect the compressor, apply power to the outdoor unit at least 6 hours prior to test operation.
Set the remote controller display mode to standard or detailed display mode. Refer to Operation
Manual for the setting method.
Notes for backlight
● The backlight will be ON for 30 seconds by pressing any button.
The initial push of the button will only turn on the backlight. While the backlight is turned on,
the buttons assigned functionality will be available.
7-1
Set the operation mode to cooling by
using the remote controller.
7-2
Press and hold
4 seconds or longer. Service settings
menu is displayed.
7-3
Select
settings menu, and press Menu/OK
button. Basic screen returns and
message "Test Operation" is displayed
at the bottom.
01_EN_3P243521-7L.indd 15
Cancel button for
Test Operation
in the service
<Basic screen>
7-
1
7-
2
Cool
Set to
68
F
Return
Clean the filter
<Service settings menu screen>
7-
3
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Setting
142
EDUS091558E
Press and hold Cancel
button for 4 seconds or
longer while the backlight
is on.
Press Menu/OK button.
15
3P243521-7L
11/27/2014 11:21:45 AM