FTX-N/U, FVXS-N, FDMQ-R Series
5.
FIELD SETTING
If optional accessories are mounted on the indoor unit, the
indoor unit setting may have to be changed. Refer to the instruc-
tion manual (optional hand book ) for each optional accessory.
SETTING
Procedure
(1) When in the normal mode, press the "
ton for at least 4 seconds, and the FIELD SET MODE is
entered.
(2) Select the desired MODE NO. with the "
(3) Push the "
(4) Push the "
NO..
(5) Push the"
are set.
(6) Push the "
MODE and return to the normal display.
(Example) If the time to clean air filter is set to "Filter Con-
tamination-Heavy", set Mode No. to "10", FIRST
CODE NO. to "0", and SECOND CODE NO. to
"02".
FIRST
MODE
CODE
NO.
NO.
Filter Contamination-Heavy/Light
(Setting for spacing time of display
time to clean air filter) (Setting for
0
when filter contamination is heavy,
10
and spacing time of display time to
clean air filter is to be halved)
Spacing time of display time to clean air filter count
3
(Setting for when the filter sign is not to be displayed)
ON/OFF input from outside (Set to enable starting/
1
12
stopping from remote.)
(VRV
Thermostat differential changeover (Set when using
system)
2
remote controller thermostat sensor.)
ON OFF
MODE NO.
TEMP
FIELD SET MODE
TIME
(3)
(4)
UP
DOWN
FAN
(5)
RESERVE CANCEL
TIMER
SECOND CODE NO.
MODE
FIRST CODE NO.
(2)
TEST
(1) (6)
TEST
MODE
" button and select the FIRST CODE NO..
UP
" button and select the SECOND CODE
DOWN
"button and the present settings
RESERVE
" button to quit the FIELD SET
TEST
DESCRIPTION OF SETTING
Long-life type
Standard type
FIRST
MODE
CODE
NO.
NO.
0
Light
10
3
12
1
Forced OFF input
(VRV
2
system)
NOTE
The SECOND CODE NO. is factory set to "01".
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial set-
tings for all the indoor units of the group are equal. (For group
control, refer to the installation manual attached to the indoor
unit for group control.)
6.
TEST OPERATION
• Perform test operation according to the instructions in the
installation manual attached to the indoor unit.
• After refrigerant piping, drain piping, and electric wiring,
operate according to the table to protect the unit.
" but-
CAUTION
1. Refer to a malfunction code in the installation manual
" button.
attached to the outdoor unit if it does not operate.
2. Refer to the installation manual attached to the outdoor unit
for individual operation system types.
Some of our product types should have the power supply
turned ON 6 hours before starting operation in order to elec-
trify crank case heater.
Refer to the installation manual attached to the outdoor unit.
Order
(1)
Open gas side stop valve.
(2)
Open liquid side stop valve.
Set to cooling with the remote controller and push "
(3)
button to start operation.
Push"
TEST
(4)
TION MODE for 3 minutes.
(5)
Push"
TEST
(6)
Confirm its function according to the operation manual.
153
SECOND CODE NO.
01
02
Approx.
Approx.
2,500 hours
1,250 hours
Heavy
Approx. 200
Approx. 100
hours
hours
Display
Do not display
ON/OFF
2°F
1°F
Operation
"button twice and operate in TEST OPERA-
"button and operate normally.
EDUS091558E
03
"
ON/OFF
6
3P510049-1A